background image

C7772A, F, G WALLPLATE TEMPERATURE SENSOR

Automation and Control Solutions

Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN  55422
customer.honeywell.com

® U.S. Registered Trademark
© 2012 Honeywell International Inc.
68-0213—04   L.L.  Rev. 01-2012 
Printed in United States

CHECKOUT

The C7772 Wallplate Temperature Sensor is immediately 

operational after wiring connections are made. Use an 

accurate thermometer of ±1°F (0.5°C) to measure the 

temperature at the sensor location. To verify sensor accuracy, 

use an ohmmeter to measure the resistance across the 

sensor wires and use Table 2 to check the accuracy of the 

specific model.

Table 2. Typical Resistance of Sensor Models.

Typical Resistance (in ohms)

C7772A

C7772F

C7772G

At 41°F (5°C)

54,200

25,392

23,467

At 50°F (10°C)

41,758

19,901

18,789

At 59°F (15°C)

32,427

15,712

15,137

At 68°F (20°C)

25,370

12,493

12,268

At 77°F (25°C)

20,000

10,000

10,000

At 86°F (30°C)

15,856

8,057

8,196

At 95°F (35°C)

12,654

6,531

6,754

Summary of Contents for C7772A

Page 1: ... and other controllers that require a 10K ohm NTC Type III sensor The C7772 sensors provide a resistive output signal proportional to sensed room or space temperature The C7772 is well suited for low profile wall mounted applications where durability and tamper proof construction is desired such as schools prisons and institutions FEATURES Low profile when mounted on industry standard utility cond...

Page 2: ...no appreciable drift thereafter No calibration of the device is possible Long term drift calibration maintenance through controller software is typically not necessary Humidity Ratings 5 to 95 rh non condensing Approvals National Electrical Code NEC Class II Fig 1 C7772 Dimensions in in mm INSTALLATION When Installing this Product 1 Read these instructions carefully Failure to follow them could da...

Page 3: ...sized from 16 to 20 AWG depending on the application The maximum length of wire from a device to the wallplate sensor is 300 ft 91m NOTE Erratic temperature readings from a sensor can be caused by the wiring practices described below These must be avoided to assure proper operation 1 Do not route temperature sensor wiring with building power wiring next to control contactors near light dimming cir...

Page 4: ...ons are made Use an accurate thermometer of 1 F 0 5 C to measure the temperature at the sensor location To verify sensor accuracy use an ohmmeter to measure the resistance across the sensor wires and use Table 2 to check the accuracy of the specific model Table 2 Typical Resistance of Sensor Models Typical Resistance in ohms C7772A C7772F C7772G At 41 F 5 C 54 200 25 392 23 467 At 50 F 10 C 41 758...

Reviews: