background image

C7007A, C7008A, C7009A FLAME ROD HOLDER & FLAME ROD ASSEMBLIES

5

60-2024—06

Protect the leadwire from excessive radiant or reflected heat. 

If any portion of the wire will be exposed to temperatures in 

excess of 125° F [51.6° C], a heat-resistant wire should be 

used (see Accessories). For wiring where temperatures do 

not exceed 125° F [52° C], wire with thermoplastic insulation 

may be used. If wire is enclosed in conduit, install a two foot 

flexible connection to the head of the unit. This permits easy 

removal of unit from combustion chamber.  

FLAME ROD REPLACEMENT

To replace flame rod in the C7008A: remove the cover, pull off 

the Rajah connector with the wiring, remove (unscrew) the 

terminal nut and the lock washer at the base of flame rod 

assembly to free the flame rod. Pull out the old flame rod and 

insert the new rod. Then replace the lock washer, screw on 

the terminal nut, push the wiring connector back on, and 

replace the cover.

Procedure is the same for C7009A except that there is no 

cover.

To replace flame rod in the C7007A: Remove the cover, 

loosen the flame rod setscrew, pull the flame rod out, insert 

the replacement rod, and tighten the setscrew. Replace the 

cover.  

A NOTE ON OIL BURNER USAGE

If the flame rod is used to prove a gas pilot on an oil 

installation, oil or soot deposits must not be allowed to form on 

flame rod insulator. Such deposits might form leakage 

resistance paths, which in turn could cause nuisance 

shutdowns of main burner.

Flame rod and porcelain insulators should be periodically 

examined for oil or soot deposits. Such deposits should be 

cleaned off before unit is put back in replace. 

The performance of the C7007A Holder (with flame rod) and 

C7008A, C7009A Flame Rod Assemblies can be determined 

by measuring the flame signal (current/voltage) during pilot 

burner operation.

Most existing Honeywell flame safeguard controls incorporate 

a flame signal jack on the amplifier or the control itself. The 

flame current measurement is made with a volt-ohm-meter 

such as the Honeywell W136A Meter or a microammeter with 

a zero to 25 microampere scale. A meter connector plug (part 

no. 196146, provided with the W136A) is used to adapt the 

W136A to the flame current jack on the flame safeguard 

control. The W136A Meter probes are connected to the two 

ends of the connector plug (red to red, black to black). The 

plug end of the connector inserts directly into the flame current 

jack of the flame safeguard control (see Fig. 11). If the flame 

safeguard control does not have a meter jack, or if a meter 

connector plug is not available, a meter can be wired in series 

with the "F" lead of the flame detector circuit. During the 

burner run cycle, the minimum acceptable flame current is two 

microamperes.

The Honeywell BCS 7700 and 7800 SERIES controls provide 

for a voltage flame signal measurement. A 20,000 ohm/volt 

meter with a zero to 5 or 10 Vdc scale is recommended for the 

BCS 7700 measurement and a one megohm/volt meter is 

suggested for the 7800 SERIES controls. The flame signal 

measurement is made by inserting the positive (red) meter 

probe into the control positive (+) jack and the negative (black) 

probe into the negative (-) jack of the BCS 7700 or the (-Com) 

jack of the 7800 SERIES control (see Figs. 12, 13). With the 

system in operation, the minimum acceptable flame signal 

voltage is 1.25 Vdc for the 7800 SERIES controls and 2.2 Vdc 

for the BCS 7700 control.

A low flame signal reading indicates the photocell is not 

receiving sufficient visible flame radiation. Low flame currents 

can be the result of an improperly positioned sight pipe, 

restricted field of view, contaminated protective window or 

focusing lens, or a defective photocell. Flame signals of 4 to 6 

microamperes for existing controls and up to 5 Vdc for the 

BCS 7700 and 7800 SERIES controls can be expected on 

good applications/installations.

Fig. 10. Measuring microamp flame signal.

Fig. 11. Measuring BCS 7700 controls flame signal 

voltage.

W136A VOLT-

OHMMETER

W136A SELECTOR

SWITCH

196146 METER

CONNECTOR

PLUG

PLUG

FLAME SIGNAL

METER JACK

PLUG-IN FLAME

SIGNAL AMPLIFIER

RED CONNECTOR

BLACK CONNECTOR

BLACK (-) METER LEAD

RED (+)

METER

LEAD

M6532A

RESET

BUTTON

B

PROGRAM

MODULE

20,000

VOLT-

OHM METER

V

O

METER

PROBES

P

FLAME

AMPLIFIER

BCS 7700 CHASSIS MODULE FOOT MOUNT

M7860

Summary of Contents for C7007A

Page 1: ...ut to an exact size The C7009A is a smaller diameter flame rod assembly with an externally threaded 1 8 27 NPT base and readily accessible Rajah electrical connection The C7009A has a 12 inch 305mm flame rod which one end is threaded and the other capable of being cut to an exact size IMPORTANT The specifications given in this publication do not include normal manufacturing tolerances Therefore th...

Page 2: ...up to 500 F 260 C for intermittent use Tested to 15 000 V R1298020 Cable For flame detector F lead wire installations in a high temper ature environment Rated up to 400 F 204 C for continu ous duty Tested for operation up to 600 V and breakdown up to 7500 V Fig 1 Dimensions in inches mm of C7007A flame rod holder Fig 2 Dimensions in inches mm of C7008A flame rod assembly Fig 3 Dimensions in inches...

Page 3: ...e flame rod will be vertical or at least angled downward A rod so installed is less likely to sag at high temperatures NOTE For extra electrode support couple a length of 1 8 inch iron pipe to the extension assembly which is already threaded internal 1 8 27 NPT C7007A only 5 The unit may also be installed so the flame rod is hori zontal or angled upward but extra support is needed for rods over 12...

Page 4: ...times greater than the area of the portion of the flame rod in contact with the flame The ratio of ground to flame contact area with a raw gas pilot is usually less than a factor of four In situations where the ground area available is inadequate the ground area must be increased There are three proven methods for providing an adequate grounding surface area a the bomb fin assembly b grounding rod...

Page 5: ...microammeter with a zero to 25 microampere scale A meter connector plug part no 196146 provided with the W136A is used to adapt the W136A to the flame current jack on the flame safeguard control The W136A Meter probes are connected to the two ends of the connector plug red to red black to black The plug end of the connector inserts directly into the flame current jack of the flame safeguard contro...

Page 6: ...C7007A C7008A C7009A FLAME ROD HOLDER FLAME ROD ASSEMBLIES 60 2024 06 6 Fig 12 Measuring 7800 SERIES controls flame signal voltage NEGATIVE METER LEAD POSITIVE METER LEAD ONE MEGOHM VOLT METER M7382 ...

Page 7: ...C7007A C7008A C7009A FLAME ROD HOLDER FLAME ROD ASSEMBLIES 7 60 2024 06 ...

Page 8: ...ROD ASSEMBLIES Automation and Control Solutions Honeywell International Inc 1985 Douglas Drive North Golden Valley MN 55422 customer honeywell com U S Registered Trademark 2011 Honeywell International Inc 60 2024 06 M S Rev 06 11 Printed in U S A ...

Reviews: