BCU 460, BCU 465 · Edition 11.19
67
Parameters
Name
Parameter
Value range Description
Factory default
settings
High temperature operation (bus)
A088
0
1
2
5
Off
Via fail-safe bus (K-SafetyLink)
Via terminal
Via fail-safe bus (K-SafetyLink) and terminal
2
A089
0
1
2
5
Off
Via fail-safe bus (K-SafetyLink)
Via terminal
Via fail-safe bus (K-SafetyLink) and terminal
2
A094
2 – 15 s
Time in seconds
A101
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
32
33
34
35
48
49
50
51
52
53
54
55
56
No function
APS Purge
APS Stage 1
APS Purge & Stage 1
APS Stage 2
APS Purge & Stage 2
APS Stage 1 & Stage 2
APS Purge & Stage1 & Stage2
APS Flameless
APS Purge & Flameless
APS Stage 1 & Flameless
APS Purge&Stage1&Flameless
APS Stage 2 & Flameless
APS Purge&Stage2&Flameless
APS Stage 1&2 & Flameless
APS Purge & Stage1&2 & Flameless
APS External Low
APS External Low & Purge
APS External High
APS External High & Purge
POC V1
POC V2
POC V3
POC V4
POC V5
TC
GPS Flame mode
GPS Flameless operation
GPS Operation
0
A102
See A101
See A101
0
A103
See A101
See A101
0