BCU 460, BCU 465 · Edition 11.19
65
Parameters
Name
Parameter
Value range Description
Factory default
settings
A041
0
1
2
3
Off; checking the positions for minimum/maximum
capacity
On; for approaching the positions for minimum/maximum
capacity
On; for approaching the position for maximum capacity
On; for approaching the position for minimum capacity
0
A042
0 – 250
Running time in seconds (can only be selected if
I020 = 2 or 3)
250
A043
0
1
2
3
Off
Post-ventilation
Low fire; actuator feedback
Low fire; time-bound
0
A048
0
1
2
4
Opens on external activation
Opens with gas stage 1
Opens with gas stage 2
Opens with V4 burner 1
0
Air actuator can be activated externally on
A049
0
1
Cannot be activated
Can be activated externally
0
Air actuator in the event of fault
A050
0
1
Cannot be activated
Can be activated externally
1
A051
0
1
2
3
Off
Tightness test before start-up
Tightness test after shut-down
Tightness test before start-up and after shut-down
0
A052
0
1
2
3
4
5
V0
V1
V2
V3
V4
V5
2
A056
3
5 – 25
30 – 3600
Time in seconds
in 5 s steps
in 10 s steps
3600
A059
2 – 25
Time in seconds
2
Proof of closure function test period
A060
0 – 6000
Time in seconds
10
A061
0 – 250
Time in seconds
0
A062
0 – 3600
Time in seconds
0