BCU 460, BCU 465 · Edition 11.19
59
Fieldbus communication
8 .4 PROFIBUS
Input bytes (BCU
➔
master)
Bit
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
0
Reset
Fr
ee
Se
e t
ab
le o
n
pa
ge 6
)
Bu
rn
er 1 fl
am
e s
ig
na
l
0 – 2
5.
5
µ
A
25
5 s
te
ps
Fr
ee
1
Start 1
2
Air ON
3
Purge ON
4
Auxiliary gas
5
Flameless
mode ON
6
Free
7
Free
BCU 460/465 basic I/O
BCU 460/465 standard I/O
Output bytes (master
➔
BCU)
Bit
Byte 0
0
Reset
1
Start 1
2
Cooling
3
Purge
4
Free
5
Free
6
Free
7
Free
I/O bytes: the programmer can choose the data to be
transferred.
Inputs
Outputs
460/465 basic I/O
1 byte
1 byte
460/465 standard I/O
4 bytes
1 byte
480 basic I/O
1 byte
1 byte
480 standard I/O
5 bytes
1 byte
Baud rate: up to 1500 kbit/s.
The max. range per segment depends on the baud rate:
Baud rate [kbit/s]
Range [m]
93.75
1200
187.5
1000
500
400
1500
200
The specified ranges can be increased by using repeat-
ers. No more than three repeaters should be connected
in series.
The specified ranges relate to bus cable type A (2-core,
shielded and twisted), e.g.
Siemens, Order No. 6XV1830-0EH10, or
Lapp cable unitronic, Order No. 2170-220T.