background image

AT20, AT40, AT72D, AT87, AT88 AT TRANSFORMERS

5

69-1641EF

Fig. 7. Secure plate to transformer with mounting 

screw.

Fig. 8. Location of mounting holes.

Mounting the AT87 Transformer

Foot Mounting (Fig. 22)

Use screws or bolts through slots in the mounting feet to 
fasten the transformer to the mounting surface.

Fig. 9. Foot mounting of AT87 Transformer.

Plate Mounting

The mounting plate allows the transformer to be mounted 
on a 4 in. by 4 in. square or 4 in. octagonal junction box.

1.

Remove the large center knockout in the mounting 
plate (see Fig. 19).

2.

Take transformer in one hand and mounting plate 
in the other hand. Keyhole slots on mounting plate 
should be up.

3.

Place large knockout in mounting plate over 
primary leadwires and end bell of transformer. The 
small tab on the bottom center of the plate fits into 
the slot in the transformer mounting feet (see Fig. 
20).

4.

Insert the mounting screw through the holes as 
illustrated. 

5.

Secure plate to transformer. Do not overtighten 
screw.

Mounting Transformer and Plate to Electrical 
Box.

The mounting plate can be mounted in 4 in. x 4 in. boxes 
with regular and irregular spaced mounting holes, and on 
4 in. octagonal boxes. 

1.

Use the screws supplied with the junction box.

2.

Place the screws through the appropriate mounting 
holes in the plate and secure the transformer and 
plate to the box. 

3.

Punch out appropriate knockouts for plate 
mounting holes, as necessary.

NOTE: Transformer should always be outside of the 

junction box.

Mounting the AT88 Transformer.

Use screws or bolts through slots in the mounting feet to 
fasten the transformer to the mounting surface. See Fig. 
10.

IMPORTANT
MOUNT
TRANSFORMER
OTHER SIDE

M9163

TRANSFORMER

PLATE

OCTAGON
BOX

M20658

IRREGULAR
4 X 4 INCH
BOX 
(MOUNTING
HOLES IN
BOX ARE
SLIGHTLY
INDENTED)

REGULAR
4 X 4 INCH
BOX (2)

IRREGULAR
4 X 4 INCH
BOX 
(MOUNTING
HOLES IN
BOX ARE
SLIGHTLY
INDENTED)

REGULAR
4 X 4 INCH
BOX (2)

OCTAGON
BOX

LOAD

N.E.C. CLASS 2

USE SCREWS OR
BOLTS THROUGH
SLOTS (4) IN
MOUNTING FEET

M20659

MOUNTING FOOT (2)

SCREW
TERMINALS
FOR
SECONDARY
CONNECTIONS

LEADWIRES
FOR PRIMARY
CONNECTIONS

Summary of Contents for AT Series

Page 1: ...sted and meet NEC Class 2 not wet Class 3 wet requirements as specified by NEMA Standard DC 20 SPECIFICATIONS Models See Table 1 Table 1 Transformer Model and Electrical Specifications a Transformer complies with 24 volt NEMA Standard DC 20 b Available with female quick connect terminals on all leadwires c Thermal fuses in primary on 208V 240V models for overload protection Model Primary Secondary...

Page 2: ...ots for direct mounting Fig 6 Fig 1 Use bolts in slots for panel mounting b Horizontal channel frame Place frame over laminations as shown in Fig 7 and bend tabs over to hold transformer securely in place Mount transformer over 3 16 in 5 mm holes in mounting feet Fig 2 Foot mounting AT20C shown c Vertical channel mounting Place frame over laminations as shown in Fig 8 and bend tabs over to hold tr...

Page 3: ...e the large center knockout in the mounting plate see Fig 19 2 Take the transformer in one hand Clamp on end bell should face you 3 Take the mounting plate in the other hand Keyhole slots should be up 4 Place large knockout in mounting plate over primary leadwires and end bell Small tab at the bottom of the center of the plate fits into the transformer mounting foot Insert mounting screw through h...

Page 4: ...6 M9188A WITH RAISED PORTION OF KNOCKOUTS FACING YOU PRY UP TOP SECTION OF LARGE KNOCKOUT BY INSERTING SCREWDRIVER FIRST AT ONE SIDE OF SLOT AND THEN AT THE OTHER SIDE 1 THEN PRY UP BOTTOM SECTION OF KNOCKOUT 2 REMOVE BOTH SECTIONS OF KNOCKOUT WITH PLIERS 3 SHADED AREAS REPRESENT KNOCKOUTS AND SCREW SLOTS USED WITH 2 X 4 INCH OR OCTAGONAL OUTLET BOXES ...

Page 5: ...te to transformer Do not overtighten screw Mounting Transformer and Plate to Electrical Box The mounting plate can be mounted in 4 in x 4 in boxes with regular and irregular spaced mounting holes and on 4 in octagonal boxes 1 Use the screws supplied with the junction box 2 Place the screws through the appropriate mounting holes in the plate and secure the transformer and plate to the box 3 Punch o...

Page 6: ...ic Fig 12 AT88 Transformer schematic CHECKOUT After installation is complete turn on power supply Placed controlled equipment into operation and observe through at least one complete cycle Make sure it functions as intended SECONDARY CONNECTIONS ARE BLUE AND YELLOW LEADWIRES BLACK IS COMMON WITH RESPECT TO THE TRANSFORMER WINDING ONLY AND NOT THE EXTERNAL CIRCUIT WHITE 120V OR ORANGE 240V COMMON 1...

Page 7: ... les fusibles sont énumérés au Tableau 1 Les composants du transformateur sont reconnus par les Laboratoires des assureurs Inc certifiés par l Association canadienne de normalisation et conformes aux exigences de câblage du Code national de l électricité NEC classe 2 pour endroits non humides et classe 3 pour endroits humides énoncées dans la norme NEMA DC 20 CARACTÉRISTIQUES TECHNIQUES Modèles Vo...

Page 8: ...e transformateur à l endroit le mieux approprié Le transformateur peut être installé de trois façons a Insérer des boulons dans les fentes dans le cas d un montage direct Fig 1 b Support en U horizontal Installer le support sur les lamelles voir la Fig 2 et replier les pattes pour fixer le transformateur Monter le thermostat en utilisant les trous de 5 mm 3 16 po dans le socle de montage c Support...

Page 9: ... la plaque au niveau de l étrier du flasque du primaire le transformateur entièrement par dessus la plaque 1 Tenir la plaque de montage dans une main les fentes en trou de serrure vers le haut et la partie soulevée de l ouverture défonçable vers soi 2 Passer les conducteurs primaires dans le trou au centre de la plaque 3 Placer le trou de la plaque par dessus l étrier attaché au flasque La vis de ...

Page 10: ...SSUS LA PLAQUE DE MONTAGE PLAQUE MONTÉE AU NIVEAU DES LAMELLES LE TROIS QUARTS DU TRANSFORMATEUR PAR DESSUS LA PLAQUE DE MONTAGE FLASQUE PLAQUE DE MONTAGE PARTIE SURÉLEVÉE DE LA GRANDE OUVERTURE DÉFONÇABLE AU CENTRE VIS DE L ÉTRIER ET ÉTRIER VIS DE MONTAGE PLAQUE DE MONTAGE BORNES À VIS DES CONNEXIONS SECONDAIRES BORNES À VIS DES CONNEXIONS SECONDAIRES CONDUCTEURS DE CONNEXIONS PRIMAIRES CONDUCTEU...

Page 11: ...trop serrer la vis Montage du transformateur et de la plaque sur une boîte électrique La plaque de montage peut être montée sur une boîte de 4 po sur 4 po avec des trous espacés régulièrement ou irrégulièrement ou une boîte octogonale de 4 po 1 Utiliser les vis fournies avec la boîte électrique 2 Insérer les vis dans les bons trous de montage de la plaque et fixer le transformateur et la plaque su...

Page 12: ...ur AT88 VÉRIFICATION Une fois l installation terminée mettre sous tension Faire fonctionner l appareil commandé et vérifier son fonctionnement pendant au moins un cycle complet Vérifier si l appareil commandé fonctionne de façon normale LES CONNEXIONS SECONDAIRES SONT LES CONDUCTEURS BLEU ET JAUNE LE FIL NOIR EST LE FIL COMMUN DE L ENROULEMENT POUR LE TRANSFORMATEUR SEULEMENT NON PAS POUR LE CIRCU...

Reviews: