L4006A,B,E,H AQUASTAT® CONTROLLERS

60-0915—5

4

OPERATION

For proper selections of settings, follow boiler 
manufacturer recommendations:

1.

High limit controller: Shuts off burner when water 
temperature exceeds high limit setting. Burner 
restarts when temperature drops to high limit setting 
minus the temperature differential. 

NOTE: If L4006E or H, see Manual Reset section.

2.

Low limit controller: Maintains minimum boiler tem-
perature for domestic hot water. Turns boiler on at 
temperature setting, less differential.

3.

Circulator controller: Prevents circulation of water 
that is not hot enough. Breaks circulator circuit at 
temperature setting minus differential and remakes 
at setting.

ADJUSTMENT

Set the differential to correspond with the boiler 
manufacturer recommendations. To adjust models with 
adjustable differential, rotate the wheel on the back of the 
snap switch until the desired reading is aligned with the V 
notch in the frame. The wheel provides an adjustment 
from 5°F to 30°F (3°C to 17°C). Replace the cover on the 
Aquastat Controller.

Adjust the control point to correspond with the boiler 
manufacturer recommendations. To  adjust, insert a 
screwdriver in the slotted screw type head located 
beneath the window in the cover. Turn the scale to the 
desired control point.

Manual Reset

When the device includes manual reset (L4006E and H), 
be sure to press the red reset button on the front of the 
case to make sure that the controller is not locked out on 
safety. When checking out the system, adjust the control 
point low enough so the temperature of the controlled 
medium reaches the high limit setting, the burner shuts 
off, and the Aquastat Controller locks out. When the 
temperature of the controlled medium drops to the high 
limit setting minus differential, push the manual reset 
button and the system should be  operative again. Reset 
control to proper high limit setting.

CHECKOUT

Check to make certain that the Aquastat Controller has 
been installed and adjusted properly. Put the system into 
operation and observe the action of the device through 
several cycles to make certain that it provides proper 
control of the system as described in the Operations 
section. Further adjustments can be made to meet more 
exact comfort requirements.

60-0915-5.fm  Page 4  Wednesday, June 20, 2007  9:16 AM

Summary of Contents for Aquastat L4006A

Page 1: ...uld damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING Electrical Shock Hazard Can cause serious injury death or e...

Page 2: ... Fig 2 Bulb in immersion well and use of adapter If the Old Well Is Unsuitable 1 Drain the system and remove the well 2 Select a new well from form 68 0040 order well separately 3 Install the new well refill the system and check for leaks 4 Loosen but do not remove the two adapter clamp screws Fig 1 5 Insert the sensing bulb into the well until it bottoms as show in Fig 2 Add heat conductive compo...

Page 3: ...th local codes and ordinances regarding wire size insulation enclosure etc See Fig 4 and 5 for typical diagrams of Aquastat Controllers used in heating systems Use these Aquastat Controllers with copper wire only Fig 4 Typical hookup for gas fired system with domestic hot water Fig 5 Hookup for oil fired summer winter hydronic system with domestic hot water This is typical where control for domest...

Page 4: ...ust the control point to correspond with the boiler manufacturer recommendations To adjust insert a screwdriver in the slotted screw type head located beneath the window in the cover Turn the scale to the desired control point Manual Reset When the device includes manual reset L4006E and H be sure to press the red reset button on the front of the case to make sure that the controller is not locked...

Page 5: ...ection 4 First Aid Measures Eye Contact Flush eyes with water for 15 minutes Remove any contact lenses and continue to flush Obtain medical attention if irritation develops and persists Skin Contact Remove excess with cloth or paper Wash thoroughly with mild soap and water Obtain medical attention if irritation develops and persists Ingestion Contact physician or local poison control center immedi...

Page 6: ...tibilities Strong oxidizing agents and halogens Hazardous Decomposition Products Carbon dioxide carbon monoxide Section 11 Toxicology Information No data available Section 12 Ecological Information Chemical Fate Information Hydrocarbon components will biodegrade in soil relatively persistent in water Section 13 Disposal Consideration Dispose of as solid waste in accordance with local state and fed...

Page 7: ...7 60 0915 5 60 0915 5 fm Page 7 Wednesday June 20 2007 9 16 AM ...

Page 8: ...l Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 60 0915 5 C H Rev 08 05 60 0915 5 fm Page 8 Wednesday June 20 2007 9 16 AM ...

Reviews: