Honeywell Aquastat L4006A Installation Instructions Manual Download Page 2

L4006A,B,E,H AQUASTAT® CONTROLLERS

60-0915—5

2

1.

Remove the old control.

2.

Refer to the cover insert of the old control to identify 
and tag each lead as it is disconnected. 

3.

Leave the old well in place if it is suitable.

If Well is Otherwise Suitable But Does Not Fit The 
L4006 Immersion Well Clamp

Use a 124904 Well Adapter (order separately, see form 
68-0040) to secure the L4006 to the old well. The adapter 
has a flange at one end for fastening the L4066 adapter 
clamp.

1.

Loosen, but do not remove, the two adapter clamp 
screws (see Fig. 1).

2.

Slide the adapter onto the capillary and short tube; 
see Fig. 2 inset.

3.

Make sure the flanged end of the adapter fits into 
the hole in the case. Position the adapter well clamp 
snugly over the flange on the adapter, then tighten 
the clamp screws.

4.

Insert the bulb into the well, as shown in Fig. 2. If 
necessary, use the heat-conductive compound as 
instructed in the IMPORTANT statement on page 1.

5.

Tighten the setscrew (if one is present in the old 
well spud) against the adapter.

Fig. 1. Internal view of L4006A,B with horizontal well. 

L4006E is the same with reset button added.

Fig. 2. Bulb in immersion well and use of adapter.

If the Old Well Is Unsuitable.

1.

Drain the system and remove the well. 

2.

Select a new well from form 68-0040 (order well 
separately).

3.

Install the new well, refill the system and check for 
leaks.

4.

Loosen, but do not remove, the two adapter clamp 
screws (Fig. 1).

5.

Insert the sensing bulb into the well until it bottoms 
as show in Fig. 2. Add heat-conductive compound, 
if necessary, as instructed in the IMPORTANT 
statement on page 1.

M4679

SETPOINT

INDICATING DIAL

DIFFERENTIAL

ADJUSTMENT

WHEEL

ADAPTER CLAMP

SCREWS

IMMERSION

WELL

MODELS WITH FIXED DIFFERENBTIALS DO NOT INCLUDE

ADJUSTING WHEEL.

VERTICALLY MOUNTED IMMERSION WELL IS ATTACHED

TO THE BOTTOM OF THE CASE.

1

2

1

2

CONTROLLER

CASE

ADAPTER

ADAPTER

CLAMP

IMMERSION

WELL SPUD

BOILER

OLD IMMERSION

WELL ASSEMBLY

BACK OF

CASE

ADAPTER

ADAPTER

CLAMP

SENSING 

BULB

HEAT-CONDUCTIVE COMPOUND

SETSCREW

CAPILLARY

TUBE

(C)

SHORT TUBE 

FITS IN CENTRAL

RECESS OF 

ADAPTER

SLIGHTLY BEND IN TUBES SHOULD HOLD BULB IN GOOD THERMAL CONTACT WITH THE WELL AT TWO OPPOSITE POINTS, AS IN (A) AND (B).

ASSURE THAT TUBES FIT FREELY IN ADAPTER SO THAT TENSION OF THE CAPILLARY TUBE AT POINT (C) 

HOLDS THE SENSING BULB IN GOOD THERMAL CONTACT WITH THE BOTTOM OF WELL AT POINT (D).

M4678

1

2

2

(D)

(B)

(A)

1

60-0915-5.fm  Page 2  Wednesday, June 20, 2007  9:16 AM

Summary of Contents for Aquastat L4006A

Page 1: ...uld damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING Electrical Shock Hazard Can cause serious injury death or e...

Page 2: ... Fig 2 Bulb in immersion well and use of adapter If the Old Well Is Unsuitable 1 Drain the system and remove the well 2 Select a new well from form 68 0040 order well separately 3 Install the new well refill the system and check for leaks 4 Loosen but do not remove the two adapter clamp screws Fig 1 5 Insert the sensing bulb into the well until it bottoms as show in Fig 2 Add heat conductive compo...

Page 3: ...th local codes and ordinances regarding wire size insulation enclosure etc See Fig 4 and 5 for typical diagrams of Aquastat Controllers used in heating systems Use these Aquastat Controllers with copper wire only Fig 4 Typical hookup for gas fired system with domestic hot water Fig 5 Hookup for oil fired summer winter hydronic system with domestic hot water This is typical where control for domest...

Page 4: ...ust the control point to correspond with the boiler manufacturer recommendations To adjust insert a screwdriver in the slotted screw type head located beneath the window in the cover Turn the scale to the desired control point Manual Reset When the device includes manual reset L4006E and H be sure to press the red reset button on the front of the case to make sure that the controller is not locked...

Page 5: ...ection 4 First Aid Measures Eye Contact Flush eyes with water for 15 minutes Remove any contact lenses and continue to flush Obtain medical attention if irritation develops and persists Skin Contact Remove excess with cloth or paper Wash thoroughly with mild soap and water Obtain medical attention if irritation develops and persists Ingestion Contact physician or local poison control center immedi...

Page 6: ...tibilities Strong oxidizing agents and halogens Hazardous Decomposition Products Carbon dioxide carbon monoxide Section 11 Toxicology Information No data available Section 12 Ecological Information Chemical Fate Information Hydrocarbon components will biodegrade in soil relatively persistent in water Section 13 Disposal Consideration Dispose of as solid waste in accordance with local state and fed...

Page 7: ...7 60 0915 5 60 0915 5 fm Page 7 Wednesday June 20 2007 9 16 AM ...

Page 8: ...l Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 60 0915 5 C H Rev 08 05 60 0915 5 fm Page 8 Wednesday June 20 2007 9 16 AM ...

Reviews: