Honeywell Aquastat L4006A Installation Instructions Manual Download Page 3

L4006A,B,E,H AQUASTAT® CONTROLLERS

3

60-0915—5

6.

Make sure the end of the well fits into the hole in the 
case. Position the immersion well clamp snugly 
over the well flange and tighten the clamp screw 
securely.

Mounting Surface Mount Model (L4006H)

The L4006H is designed for surface mounting on piping or 
tank and can be mounted in any position.

When mounting the L4006H on piping, the pipe should be 
1 in. (25 mm) diameter or larger for accurate temperature 
sensing.

1.

Remove any insulation from the pipe. 

2.

Thoroughly scrape off all scale, rust or paint. 

3.

Mount controller as shown in Fig. 3 using adjustable 
12 in. (294 mm) pipe strap furnished.

When mounting the L4006H on a tank, use a pipe strap of 
appropriate length, approximately 6-10 ft (17.6- 29.4m) for 
the tank (not provided). Fit the pipe strap through the slot 
in the mounting bracket. See Fig. 3.

Fig. 3. Mount L4006H directly on surface.

Wiring

WARNING

Electrical Shock Hazard.
Can cause serious injury, death or equipment 
damage.

Disconnect power supply before connecting wiring 
to avoid electrical shock or equipment damage.

All wiring must comply with local codes and ordinances 
regarding wire size, insulation, enclosure, etc. See Fig. 4 
and 5 for typical diagrams of Aquastat® Controllers used 
in heating systems.

Use these Aquastat Controllers with copper wire only.

Fig. 4. Typical hookup for gas-fired system with 

domestic hot water.

Fig. 5. Hookup for oil-fired, summer-winter, hydronic 

system with domestic hot water. This is typical where 

control for domestic hot water is added, or where 

each Aquastat Controller is mounted in a separate 

location.

M8771A

ENCLOSED

SENSING BULB

PIPE

12 IN.

ADJUSTABLE

PIPE 

STRAP

AQUASTAT

CONTROLLER CASE

MOUNTING

BRACKET

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND

OVERLOAD PROJECTION AS REQUIRED.

USE L4006E FOR MANUAL RESET.

1

2  

M2856

2  

L1 

(HOT)
L2

1

24 VOLT

THERMOSTAT

LOW WATER

CUTOFF

PRESSURE 

CONTROL

L4006A OR

L4007A

LOW LIMIT

AQUASTAT¨

CONTROLLER

GAS

VALVE

PILOTSTAT¨

CONTROL

1

2

3

4

T

T

IGNITION

BURNER

L4006B OR L4007B

CIRCULATOR

AQUASTAT¨ 

CONTROLLER

CIRCULATOR

L4006A OR L4007A LOW LIMIT

AQUASTAT¨ CONTROLLER

L1

(HOT)

L2

L4006A OR L4007A

HIGH LIMIT

AQUASTAT¨

CONTROLLER

24 VOLT

THERMOSTAT

RA832A

SWITCHING RELAY

PROTECTORELAY¨

CONTROL

POWER SUPPLY.  PROVIDE DISCONNECT MEANS AND

OVERLOAD PROTECTION AS REQUIRED.

USE L4006E FOR MANUAL RESET.

1

2  

M2855A

T

T

X

X

4

2

1

1

2  

60-0915-5.fm  Page 3  Wednesday, June 20, 2007  9:16 AM

Summary of Contents for Aquastat L4006A

Page 1: ...uld damage the product or cause a hazardous condition 2 Check the ratings given in the instructions and on the product to make sure the product is suitable for your application 3 Installer must be a trained experienced service technician 4 After installation is complete check out product operation as provided in these instructions WARNING Electrical Shock Hazard Can cause serious injury death or e...

Page 2: ... Fig 2 Bulb in immersion well and use of adapter If the Old Well Is Unsuitable 1 Drain the system and remove the well 2 Select a new well from form 68 0040 order well separately 3 Install the new well refill the system and check for leaks 4 Loosen but do not remove the two adapter clamp screws Fig 1 5 Insert the sensing bulb into the well until it bottoms as show in Fig 2 Add heat conductive compo...

Page 3: ...th local codes and ordinances regarding wire size insulation enclosure etc See Fig 4 and 5 for typical diagrams of Aquastat Controllers used in heating systems Use these Aquastat Controllers with copper wire only Fig 4 Typical hookup for gas fired system with domestic hot water Fig 5 Hookup for oil fired summer winter hydronic system with domestic hot water This is typical where control for domest...

Page 4: ...ust the control point to correspond with the boiler manufacturer recommendations To adjust insert a screwdriver in the slotted screw type head located beneath the window in the cover Turn the scale to the desired control point Manual Reset When the device includes manual reset L4006E and H be sure to press the red reset button on the front of the case to make sure that the controller is not locked...

Page 5: ...ection 4 First Aid Measures Eye Contact Flush eyes with water for 15 minutes Remove any contact lenses and continue to flush Obtain medical attention if irritation develops and persists Skin Contact Remove excess with cloth or paper Wash thoroughly with mild soap and water Obtain medical attention if irritation develops and persists Ingestion Contact physician or local poison control center immedi...

Page 6: ...tibilities Strong oxidizing agents and halogens Hazardous Decomposition Products Carbon dioxide carbon monoxide Section 11 Toxicology Information No data available Section 12 Ecological Information Chemical Fate Information Hydrocarbon components will biodegrade in soil relatively persistent in water Section 13 Disposal Consideration Dispose of as solid waste in accordance with local state and fed...

Page 7: ...7 60 0915 5 60 0915 5 fm Page 7 Wednesday June 20 2007 9 16 AM ...

Page 8: ...l Inc Honeywell Limited Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley MN 55422 Scarborough Ontario M1V 4Z9 customer honeywell com U S Registered Trademark 2005 Honeywell International Inc 60 0915 5 C H Rev 08 05 60 0915 5 fm Page 8 Wednesday June 20 2007 9 16 AM ...

Reviews: