Warning
Note
Capabilities, Connection
14
Typical Wiring
Conductivity measurement with Honeywell
5000TC toroidal conductivity sensor
The Honeywell 5000TC toroidal conductivity sensor
is used to measure low to highest conductivity val-
ues. It can be used for measurements in safe areas.
WHITE
BLUE
YELLOW
GREEN
RED
SHIELD
toroidal
cond. sensor
5
4
2
1
3
temp
lo
hi
lo
hi
send
receive
WT
BL
YW
GN
shield
RD
8
7
6
T1
T2
n.c.
Fig. 9
Conductivity measurement with Honeywell
5000TC toroidal conductivity sensor
The Honeywell 5000TC toroidal
conductivity sensor may only be
used in combination with the
APT2000TC-0(H)-00 Transmitter.
For special mounting conditions of
the sensor, the cell factor can vary
between 4.0 and 4.5. Therefore the
user should perform a wet calibra-
tion of each new sensor to deter-
mine the exact cell factor.
Settings for Honeywell 5000TC toroidal conductivity
sensor
Menu
Setting
Temp probe
conf
1200
Pt 1000
Cell factor
cal
1100
4.44