4. OPERATION
Fault relay configuration example
Requirement:
Normally De-energised, Non-Latching with the contact Normally Closed.
Implementation:
Use the
Configure Relays
menu option to set the
Fault
relay operation
requirement. Place the jumper on the
J1
link to set the contact operation as follows:
This circuit diagram shows this.
Normally
Closed
Normally
Open
Fault Common
Fault
J1
Fault
Alarm 1
Alarm 2
SK6
6
5
4
3
2
1
Fault
Relay
(Relay in
de-energised
state)
Other relays
similar
J2
J3
J1