– 2 –
– 3 –
1. Remove the smoke detector from its
mounting plate by twisting the detector
counterclockwise. If you are replacing
batteries, remove the existing batteries from
their compartments and disconnect the
battery clips.
2. Install the new 9-volt alkaline batteries in
their respective compartments as follows:
Snap the battery contacts onto the terminals
of the first battery (be sure to observe
correct polarity and do not force battery
clips). Holding the contacts on the battery,
install the battery into its compartment.
Make sure the battery is fully seated (see
Figure 1).
Connect the second 9-volt alkaline
battery in a similar manner and install it in
the second compartment.
3. Re-install the smoke detector onto the
mounting plate by turning it clockwise,
and test its operation as described in the
TEST section.
4. The LED indicator should flash about
once every 40 seconds, indicating normal
operation. If the batteries are not installed
correctly, the smoke detector will not
function. If the unit appears not to be
sending a signal during any of the tests,
check for correct battery installation.
Note:
If the detector’s ID has not been programmed into the system (i.e., this is an initial
detector installation), refer to the
PROGRAMMING
section below and perform the ID
“enrolling” procedure before mounting or testing the detector.
Programming
The control system must “enroll” the smoke detector’s ID during installation of the system. The
control should be programmed to “enroll” the 5806 as an “RF” type unit (i.e., supervised RF),
with a loop number of "1." With the control in the programming mode, you can either manually
enter the serial number or transmit from the device (push the "Enroll" button [see Figure 1],
install the battery, etc.). See the control unit’s installation instructions for further details.
Be sure to verify that the detector has been enrolled into the system by using the procedure
provided in
TESTING THE SMOKE DETECTOR section on page 6.
If a “low battery” message is displayed and you suspect that the batteries are not actually low,
remove both batteries, wait 20 seconds, re-insert them, and re-test the detector. Repeat this
procedure, if necessary.
Tamper Protection
For tamper protection, cut the wire jumper indicated in Figure 1. After the detector has been
mounted, a magnet must then be installed on the wall or ceiling next to the detector.
To ensure proper positioning of the magnet after the detector has been mounted, place a light
pencil mark on the side of the detector near the center of the reed switch (see Fig. 1).
“ENROLL” BUTTON
(INSIDE OPENING).
PUSH (WITH SMALL
SCREWDRIVER) TO
SEND “FAULT”.
CUT JUMPER
FOR TAMPER
LOCATION OF “ENROLL” BUTTON
AND “TAMPER” JUMPER
REED SWITCH
9 VOLT
BATTERY
COMPARTMENTS
INDEXING
MARK
HOLDING TABS.
LOCKING TABS ON MOUNTING PLATE SLIDE BENEATH
THESE TABS (DETECTOR IS LATCHED ONTO MOUNT-
ING PLATE BY TURNING CLOCKWISE)
*
ONLY IF TAMPER
MAGNET WILL BE
USED
MAGNETIC REED
SWITCH
PLACE LIGHT
PENCIL MARK
HERE*
INDEXING
MARK
“ENROLL”
BUTTON
9V
BA
TTER
Y
9V
BATTER
Y
ADEM
CO
Model
No. 5
806
Figure 1. Bottom View of Smoke Detector (without mounting plate)
Mounting the Smoke Detector
First, determine the best location for the
smoke detector (one that provides strong
wireless transmission paths AND proper
smoke detector protection). See
RECOMMENDED LOCATIONS FOR
SMOKE DETECTORS (on next page).
A good RF transmission path must be
established from the proposed mounting
location before permanently installing the
detector. To check, perform the test in
TESTING THE SMOKE DETECTOR.
Mounting Locations
Detectors should be located as close to the
center of the ceiling as possible. If this is
not practical, detectors may be located on
the ceiling up to 4 inches (10cm) from the
ceiling-wall junction. Do not install near
forced-air heating or air conditioning ducts
(outlets or returns). For sloped, gabled, or
high-peaked ceilings, detectors must be
mounted between 4 and 6 inches (10 and
15cm) from the highest point in the ceiling.
Detectors may also be wall-mounted.
Check with your local Fire Department
about code requirements. Wall-mounted
detectors should be located 4–6 inches
(10–15 cm) from the ceiling.
In mobile homes, battery-operated
detectors are not generally installed by the
manufacturer. Mount detectors ONLY on an
interior wall.
1.
Once a suitable location has been
determined, install the mounting plate
on the ceiling or on the wall. Use the
two screws and anchors provided.
2. Latch the detector onto the mounting
plate as follows: Position the detector
onto the plate, mating the small center
post on the detector with the "dimple" at
the center of the mounting plate, and
aligning the index marks on the sides of
the plate and the detector. Then turn the
detector in a clockwise direction so that
the holding tabs on the detector engage
the locking tabs on the mounting plate.
3. If the tamper has been enabled (as
indicated previously), a magnet (No.
39WH-M) should be mounted on the wall
or ceiling surface next to the detector
(1/4” max) in the specified location (see
Fig. 2).
4. Test the detector immediately after
completing the installation and refer to
the control system's instructions for
additional information concerning the use
of wireless smoke detectors.
DEAD AIR
SPACE
4 IN.
(10 cm)
CEILING
BEST IN
CORNER
ACCEPTABLE
HERE
ACCEPTABLE
HERE
NOTE:
MEASUREMENTS
SHOWN ARE TO THE
CLOSEST EDGE OF
THE DETECTOR.
SIDE WALL
NEVER
HERE
4 IN.
6 IN.
(10 cm)
(15 cm)
SLOTTED HOLES
FOR MOUNTING
SCREWS
INDEXING MARK
LOCKING TABS
(USED FOR SECURING
SMOKE DETECTOR
TO MOUNTING PLATE)
INDEXING MARK
NOTE:
OTHER SIDE FACES CEILING OR WALL
(THE WORDS “SINGLE GANG” MUST FACE
AWAY FROM MOUNTING SURFACE)
ACE).
TEST BUTTON
INSTALLATION OF MAGNET (FOR TAMPER PROTECTION
)
INDEXING MARK
1/4" MAX
No.39WH-M MAGNET
NOTE: MAGNET IS
MOUNTED NEXT TO
DETECTOR ON SIDE
OPPOSITE TEST
BUTTON.
Figure 2. Mounting Details