SETTING-UP THE DETECTOR
PULSE WIDTH JUMPER SETTING
LED ENABLE JUMPER SETTING
PET IMMUNITY JUMPER SETTING
PIR SENSITIVITY ADJUSTMENT
POTENTIOMETER
– adjustment according to
protected area range.
Use the potentiometer to adjust the detection
range between 68% and 100% (factory set to
84%). Rotate the potentiometer clockwise to
increase range, counter-clockwise to decrease
range.
WIRE SIZE REQUIREMENTS
Use #22 AWG (0.5 mm) or wires with a larger
diameter. Use the following table to determine
required wire gauge (diameter) and length of wire
between the detector and the control panel.
Wire Length m 200 300 400 800
Wire Diameter mm .5 .75 1.0 1.5
Wire Length ft. 800 1200 2000 3400
Wire Gauge # 22 20 18 16
TESTING
BRACKET INSTALLATION OPTION
TEST PROCEDURES
WAIT FOR ONE MINUTE OF WARM UP TIME
AFTER APPLYING 12 VDC POWER.
CONDUCT TESTING WITH THE PROTECTED
AREA CLEARED OF ALL PEOPLE.
Walk test
1. Remove front cover.
The pulse jumper must be in position 1. The
LED must be enabled.
2. Replace the front cover.
3. Start walking slowly across the detection zone.
4. Observe that the detector
’
s LED lights
whenever motion is detected.
5. Allow 5 sec. between each test for the detector
to stabilize.
6. After the walk test is completed, the LED may
be disabled.
NOTE:
Walk tests should be conducted, at least once a
year, to confirm proper operation and coverage of
the detector.
WALL AND CEILING INSTALLATION REPLACING THE LENS
ADDING A FILTER
1. Remove the front cover.
2. Using a small flat screwdriver, press on left
and right snaps of the lens and pull the lens
out from its place (front cover side).
3. Replace a new lens.
4. Push the lens to its place by pressing again
from outside of the front cover until a click is
heard.
5. Replace front cover.
Filter for immunity of 6000 Lux
(Adding the filter may reduce sensitivity by 10%)
TECHNICAL SPECIFICATION
MODEL
Activ8 PIR
Detection Method
Quad (Four element) PIR
Power Input
9.6 to 16 VDC
Current Draw
Standby: 8mA (
±
5%)
Active: 10mA (
±
5%)
Temperature
Compensation
YES
Pulse Width
Adjustable
Alarm Period
2 sec (
±
0.5sec)
Alarm Output
N.C 28VDC 0.1 A with 27Ohm series protection resistor
Tamper Switch
N.C 28VDC 0.1A with
10 Ohm series protection resistor - open when cover is removed
Warm Up Period
60sec (
±
5sec)
LED Indicator
LED is ON during alarm
Operating Temperature
-20
°
C to +60
°
C
(-4
°
F to +140
°
F)
RFI Protection
30V/m 10 - 1000MHz
EMI Protection 50,000V of electrical interference from lightning through power line
Dimensions
90mm x 59mm x 37mm
(3.54
’’
x 2.32
’’
x 1.46
’’
)
Weight
40gr (1.4oz)
Honeywell Security & Communications
(UK64)Newhouse Industrial Estate
Motherwell
Lanarkshire
ML1 5SB
Tel +44 (0)1698 738200
Fax +44 (0)1698 738300
Tech Support: +44 (0)844 8000 235
intruder
/
uk
/
curity
se
/
com
.
honeywell
.
www
.
Very stable environment
Jumper #1 = ON
Without PET
Moderate nuisance situation
Jumper #2 = ON
PET up to 15 kg (33.1 lb)
Relatively high chance of false
alarms
Jumper #3 = ON
PET up to 25 kg (55 lb)
LED ON
LED OFF
Immunity to an
animal up to 15 kg
Immunity to an
animal up to 25 kg
In EN 50131-2-2 and PD6662:2010 Grade 2 compliant installations, do not use swivel mount brackets