4.4 SBUS Wiring
This section contains information on calculating SBUS wire distances and the types of wiring configurations (Class B).
4.4.1 Calculating Wiring distance for SBUS modules
The following instructions will guide you in determining the type of wire and the maximum wiring distance that can be used with control
panel SBUS accessory modules.
To calculate the wire gauge that must be used to connect SBUS modules to the control panel, it is necessary to calculate the total worst
case current draw for all modules on a single 4-conductor bus. The total worst case current draw is calculated by adding the individual
worst case currents for each module. The individual worst case values are shown in the table below..
After calculating the total worst case current draw, Table 4.2 specifies the maximum distance the modules can be located from the panel
on a single wire run. The table insures 6.0 volts of line drop maximum. In general, the wire length is limited by resistance, but for heavier
wire gauges, capacitance is the limiting factor.
These cases are marked in the chart with an asterisk (*). Maximum length can never be more than 6,000 feet, regardless of gauge used.
(The formula used to generate this chart is shown in the note below).
Wiring Distance calculation example:
Suppose a system is configured with the following SBUS modules:
2 - Module 5860
Remote LCD Annunciator
1 - 5496 NAC Expander
1 - 5865 LED Fire Annunciator
1 - 5824 Serial/Parallel Printer Interface Module
The total worst case current is calculated as follows:
NOTE:
Total worst case current draw on a single SBUS cannot exceed 1 amp
Model Number
Worst Case Current Draw
5860, 6855 or 6860 LCD Annunciator
.100 amps
5824 Serial/Parallel Printer Interface Module
.040 amps
5880 LED I/O Module
.250 amps
5865 LED Fire Annunciator
.200 amps
5496 NAC Expander
.010 amps
SK-NIC Network Interface Card
.021 amps
CELL-MOD/CELL-CAB-SK
.145 amps
SK-F485C Fiber Converter
.125 amps
Table 4.1 : SBUS Device Current Draw
Wiring Distance: SBUS Modules to Panel
Total Worst Case
Current Draw (amps)
22 Gauge
18 Gauge
16 Gauge
14 Gauge
0.100
1852 ft.
4688 ft.
* 6000 ft.
* 6000 ft.
0.200
926 ft.
2344 ft.
3731 ft.
5906 ft.
0.300
617 ft.
1563 ft.
2488 ft.
3937 ft.
0.400
463 ft.
1172 ft.
1866 ft.
2953 ft.
0.500
370 ft.
938 ft.
1493 ft.
2362 ft.
0.600
309 ft.
781 ft.
1244 ft.
1969 ft.
0.700
265 ft.
670 ft.
1066 ft.
1687 ft.
0.800
231 ft.
586 ft.
933 ft.
1476 ft.
0.900
206 ft.
521 ft.
829 ft.
1312 ft.
1.000 (Max)
185 ft.
469 ft.
746 ft.
1181 ft.
Table 4.2 : Wiring Distances Per Wire Gauge Using Copper Wire
NOTE:
The following formulas wee used to generate the wire distance chart.
Summary of Contents for 6808
Page 13: ...6808 Manual P N LS10146 001SK E C 09 28 2017 13 Introduction ...
Page 67: ...6808 Manual P N LS10146 001SK E C 09 28 2017 67 Common Communication Link ...
Page 97: ...6808 Manual P N LS10146 001SK E C 09 28 2017 97 Programming Overview ...
Page 143: ...6808 Manual P N LS10146 001SK E C 09 28 2017 143 Testing and Troubleshooting ...
Page 159: ...6808 P N LS10146 001SK E C 09 28 2017 159 ...
Page 161: ...6808 P N LS10146 001SK E C 09 28 2017 161 ...
Page 163: ...6808 P N LS10146 001SK E C 09 28 2017 163 ...
Page 165: ...6820 6820EVS Manual P N LS10144 001SK E C 09 28 2017 165 ...
Page 168: ...Cut Along the Dotted Line ...
Page 169: ......