6
Rated Output
(Running Amps)
Maximum Surge Capability
Size (kW)
240V 1Ø
208V 3Ø
240V 3Ø
480V 3Ø
240V 1Ø
208V 3Ø
240V 3Ø
480V 3Ø
11
42
n/a
n/a
n/a
92
n/a
n/a
n/a
15
71
n/a
n/a
n/a
130
n/a
n/a
n/a
20
83
n/a
n/a
n/a
185
n/a
n/a
n/a
60
250
208
180
90
350
251
218
136
70
292
243
210
105
550
471
408
201
80
333
278
240
120
550
466
404
212
150
625
520
451
226
1214
1334
1156
624
Rated Output
(Running Amps)
Maximum Surge Capability
Size (kW)
240V 1Ø
208V 3Ø
240V 3Ø
480V 3Ø
240V 1Ø
208V 3Ø
240V 3Ø
480V 3Ø
25
113
87
75
n/a
265
221
192
n/a
35
146
121
105
52
225
210
182
87
45
188
156
135
68
321
269
233
112
70
292
243
210
105
550
471
408
201
100
417
347
300
150
738
452
426
261
130
542
451
390
195
1088
885
767
419
Note: All nominal ratings based upon LP fuel. Refer to specification sheet for
NG ratings and deration adjustments for ambient temperature and altitude.
Honeywell Generators (Operating at less than 3600 RPM)
Honeywell Generators (Operating at 3600 RPM)
Table 3
Surge Capability
Summary of Contents for 6261