System Capacity – load Calculator
DIRECTIONS FOR NEC 2011, ARTICLE 220, PART IV
220.80 Optional Feeder and Service Load Calculations (RESIDENTIAL)
NFC REFERENCE
SECTION CAN BE USED FOR DWELLING UNITS
220.82 (A)
Served by a single feeder conductor (generator)
• 120/240 volt or 208Y/120 volt service
• Ampacity of 100 amps or greater the calculated load will be the result of adding
• 220.82 (B) General Loads, and
220.82 (B)
• 220.82 (C) Heating and Air-Conditioning Load
220.82 (C)
• Calculated neutral load determined by 220.61 . (Additional 70% demand factor can be
taken for cooking appliances and dryers when tables 220.54 and/or 220.55 are used)
GENERAL LOADS
220.82 (A)
General Lighting and General-Use Receptacles
• Calculate at 3 VA per square foot
220.82 (B) (1)
• Use exterior dimensions of the home to calculate square footage – do not include
open porches, garages or unused or unfinished spaces not adaptable for future use.
• Add 20-amp small appliance & laundry circuits @ 1500 VA each
220.82 (B) (2)
Calculate the following loads at 100% of nameplate rating
220.82 (B) (3)
• Appliances fastened in place, permanently connected or located on a specific circuit
220.82 (B) (3) a
• Ranges, wall-mounted ovens, counter-mounted cooking units (Tables 220.54 & 220.55)
220.82 (B) (3) b
• Clothes dryers not connected to the laundry branch circuit
220.82 (B) (3) c
• Water heaters
220.82 (B) (3) d
• Permanently connected motors not included in Heat & Air-Conditioning Load section
220.82 (B) (4)
HEATING & AIR-CONDITIONING LOADS
220.82 (C )
Include the
largest
of the following six selections (kVA load) in calculation
Air Conditioning and Cooling
220.82 (C) (1)
• 100% of nameplate rating
Heat Pumps Without Supplemental Electric Heating
220.82 (C) (2)
• 100% of nameplate rating
Heat Pumps With Supplemental Electric Heating
220.82 (C) (3)
• 100% of nameplate rating of the heat pump compressor*
• 65% of nameplate rating of supplemental electric heating equipment
- If compressor & supplemental heat cannot run at the same time
do not include the compressor
Electric Space Heating
• Less than 4 separately controlled units@ 65% of nameplate rating
220.82 (C) (4)
• 4 or more separately controlled units @ 40% of nameplate rating
220.82 (C) (5)
• 40% of nameplate rating if 4 or more separately controlled units
Electric Thermal Storage (or system where the load is expected to be
220.82 (C) (6)
continuous at nameplate rating
• 100% of nameplate rating
• Systems of this type cannot be calculated under any other section of 220.82 (C).
LOAD CALCULATIONS
General Lighting Load
3VAxft
2
• Small Appliance & Laundry Circuits
+ 1500 VA per circuit
• General Appliances & Motors (1 00% rated load)
+ Total general appliances
• Sum of all General Loads
= Total General Load (VA)
APPLY DEMAND FACTORS
- First 10 kVA@ 100%
= 10,000 VA
- Remainder of General Loads @ 40%
(Total VA -10,000) x .40
= Calculated General Load (VA)
• HEAT I A-C LOAD@ 100%
Largest Heat or A-Q Load (VA)
= TOTAL CALCULATED LOAD
Converting VA TO kW (Single-phase applications with 1.0 power factor only) 1 kVA = 1 kW