Menu 5: Enter Zone Number
NOTES:
This menu starts Zone Programming, which lets you
program basic zone attributes. Enter the desired zone
number at this prompt, then press [
∗
]. The Zone
Programming page (menu 6) appears.
When all zones have been programmed, enter
00
to
advance to the Quit menu.
Zone Number
Enter Zone No
01
Programming Option
Entries
Field
a.
Zone Number
Control
Wired Zone
RF Zones
Vista-20P and Vista-21iP:
01-08
;
09-48
†
09-48
;
49-64
††
95
,
96
,
99
†††
Vista-15P:
01-06
;
09-24
†
09-34
;
49-56
††
95
,
96
,
99
†††
Vista-10P:
01-06
09-24
95
,
96
,
99
†††
49-56
††
†
Zone Expander Zones; †† RF button zones; ††† Emergency zones
[
∗∗∗∗
] = continue programming the selected zone
00
= go to Quit menu
∗
56
Menu 6: Zone Programming
NOTES:
Pressing [
∗
] at the Zone Number prompt displays the
Zone Programming page. To program additional zone
attributes, or to use any other menu mode of
programming, use standard control panel programming
mode (installer code + 800).
DISPLAY NOTE:
Typical hardwired zone shown in the
example display. For wireless zones, the Resp / Config line is
replaced by the serial number entry line:
S/N Axxx – xxxx
Loop x
Zone Programming
#01
Type: 09
Fire
Send Report: Y
Part 1
Input Type:
Hardwired
Resp: 350mS
Config: EOL
Library
000 000 000
Disp :
xxxxxxxxxxxxxxxx
Zone Programming
Programming Option
Entries
Field
Notes
a.
Zone Type
|
∗
56
Enter the 2-digit Zone Type from the table below.
00
= Not used
07
= 24-Hr Audible
20
= Arm–STAY*
01
= Entry/exit #1
08
= 24-Hr Aux
21
= Arm–AWAY*
02
= Entry/exit #2
09
= Fire
22
= Disarm*
03
= Perimeter
10
= Interior w/Delay
23
= No Alarm Resp
04
= Int. Follower
12
= Monitor Zone
24
= Silent Burglary
05
= Day/Night
14
= Carbon Monoxide
77
= Keyswitch
06
= 24-Hr Silent
16
= Fire w/Verify
81
= AAV Mon. Zone
To disable the current zone, enter 00.
Press [
∗
] to advance.
b.
Send Report
∗
56
0
= No – do not send report
1
= Yes – send report
c.
Partition
∗
56
1
= parition 1
2
= partition 2
3
= partitions 1 & 2
Applies only to partitioned controls.
Press [
∗
] to advance.
d.
Input Type
∗
56
For built-in hardwired zones, the input type
automatically displays “Hardwired.” For wireless
and auxiliary wired zones, select the input type:
2
= Aux (Aux wired zone; ex. 4219, 4229)
3
= RF. Trans. (supervised RF transmitter)
4
= Unsupv. RF (unsupervised RF transmitter)
5
= RF Button (Unsupervised Button RF)
Press [
∗
] to advance.