Menu 3: Enabling System Reports (for ADEMCO Contact ID
®
reporting only)
NOTES:
This menu lets you enable various system reports if
ADEMCO Contact ID
®
format is being used by
selecting yes or no for each report. If another report
format is desired, use standard control panel
programming mode (installer code + 800) to program
these reports. Refer to the field number column for the
respective programming field in standard programming
mode.
System Reports
RF Jam
N
Cancel
N
Log Full
N
Exit Error
N
P1
P2
P3
Open Report N
N
N
Close Away
N
N
N
Close Stay
N
N
N
System Reports
Programming Option
Event
Field
Notes
a.
RF Jam Report
∗
22
To enable/disable a report:
0
= No
1
= Yes
To toggle the entry, use the
D
key.
Dashed boxes:
Indicates the entry is available
only for partitioned systems (ex. VISTA-20P,
VISTA-21iP).
b.
Cancel Report
∗
68
c.
Event Log Full Report
∗
89
d.
Exit Error Report
∗
59
e.
Open Report
Part 1
Part 2
Part 3
∗
65
f.
Close Away Report
(Arm Away)
Part 1
Part 2
Part 3
∗
66
g.
Close Stay Report
(Arm Stay)
Part 1
Part 2
Part 3
∗
66
Menu 4: Timing and Miscellaneous Options
NOTES:
This menu lets you set entry/exit delays, alarm
sounding timeouts, installer code, and enable the auto-
stay option. To program other options, use standard
control panel programming mode (installer code + 800).
Refer to the field number column for the respective
programming field in standard programming mode.
Timing / Misc
P1
P2
Exit Delay
60
60
Entry 1 Delay
30
30
Entry 2 Delay
30
30
Al ar m So un d Ti me :
4M
Fire Snd. Timeout
N
Installer Code
xxxx
Auto Stay:
Part 1 & 2
Timing and Miscellaneous Options
Scroll Backward:
Use the
C
key;
Scroll Forward:
Use the
D
key.
Dashed boxes
: Indicates the entry is available only for partitioned systems (ex. VISTA-20P, VISTA-21iP).
Programming Option
Entries
Field
Notes
a.
Exit Delay
| |
Part. 1
Part. 2
∗
34
00 - 96
= 0 - 96 seconds
97
= 120seconds
SIA Controls: Entries less than 45 result in 45-sec. delay.
b.
Entry Delay 1
| |
Part. 1
Part. 2
∗
35
00 - 96
= 0 - 96 seconds
98
= 180seconds
97
= 120seconds
99
= 240seconds
SIA Controls: Entries less than 30 result in 30-sec. delay.
c.
Entry Delay 2
| |
Part. 1
Part. 2
∗
36
See Entry Delay 1 for entries.
d.
Alarm Sounder (Bell)
Timeout
∗
33
0
= none
3
= 12 min
1
= 4 min
4
= 16 min
2
= 8 min
e.
Fire Alarm Sound
Timeout
[Fire Snd. Timeout]
∗
32
0
= Yes - sound stops at timeout set in field
∗
33
1
= No - no timeout
f.
Installer
Code
| | |
∗
20
4 digits,
0000-9999
g.
Auto-Stay
∗
84
0
= no
2
= part. 2 only
1
= part. 1 only
3
= part. 1 & part 2