background image

     5898 Wireless DUAL TEC

®

 Motion Sensor  - Installation Instructions 

FR-Canadian 

 

PRELIMINARY DRAFT 5/18/09

 

3 -

 

1

    

 

SELECT MOUNTING LOCATION (See 

A

Additional guidelines for animal immunity: 

 

Mount the center of the sensor at 2.3 m (7.5 feet) high. 

 

Set the sensor to the Lowest or Low sensitivity (see step 6a). 

 

Install Animal Immune lens (5-532-489-01 - see Lens Change 
Instructions on page 3). 

 

Install the look-down mask (see Step 6a). 

 

Install the sensor where animals cannot come within 1.8 m (6 ft) of 
the sensor by climbing on furniture or other objects. 

 

Aim the sensor away from stairways, furniture or other objects that 
can be climbed on by pets. 

 

TEST the installation site to determine the exact level of attainable 

animal immunity.  

2

  

REMOVE THE FRONT HOUSING (SEE 

B

3

    

 

SELECT THE RANGE, SENSITIVITY AND PROTOCOL (SEE 

C

)

 

4

  

CONNECT THE BATTERIES (SEE 

D

5

  

REGISTER THE SENSOR TO THE PANEL 

 

Refer to the control panel’s manual and the programming tool manual 
for information on registering wireless devices. 

Once you enter the sensor serial number into the panel programming, 
select the desired loop for that zone.   

Serial # 

/ LOOP 

 

 

Serial #1 

/ Loop 1 

High Sensitivity 

No Animal Immunity 

Pulse Count 1 

Serial #1 

/ Loop2 

Low Sensitivity / Animal 

Immunity [23 kg (50 lb.) / 45 

kg (100 lb.)] 

Pulse Count 2 

Serial #2 

/ Loop 1 

Low Temperature Trip 

When temperature drops 

below 7° C ± 2° C   

(45° F ± 4° F) for 5 minutes 

Low Temp Restoral 

When temperature 

rises + 2° C  

(+ 3° F) above low 

temperature trip point 

Serial #2 

/ Loop 2 

High Temperature Trip 

When temperature rises 

above  35° C ± 2° C   

(95° F ± 4° F) for 5 minutes 

Low Temp Restoral 

When temperature 

crops - 2° C  

(- 3° F) below high 

temperature trip point 

 

6

  

MOUNT THE SENSOR (SEE 

E

7

  NORMAL WALK TEST– 10 MINUTES 

Normal walk test mode activates every time the front cover is closed 
and remains active for 10 minutes.  For an additional 10 minutes of 
walk test time, remove and replace the front cover.  In walk test mode, 
the LED is always enabled.  
Walk through the detection area and observe the LED.  
If necessary, adjust the microwave range, pulse count or sensitivity 
setting. (For LED activation meaning, refer to the LED Indicator table.) 

8  

MICROWAVE WALK TEST – 10 MINUTES

 

1. Set the Microwave Walk Test DIP switch to ON, or toggle it ON and 

OFF. 

2. Set Range Adjustment potentiometer to 25% and replace the cover.   
3. Walk through the detection area and observe the LED.  
4. If necessary, adjust the potentiometer until desired detection range 

is obtained. (For LED activation meaning, refer to the LED Indicator 
table.) 

Power Up

Trouble or Anti-Mask

Fast Blinking Red (LED Enabled 
or Disabled)

Condition

Indicator LED

Slow Blinking Red (will finish within 
60 seconds)

Indicator LEDs

Normal Walk Test

Red ON for 3 seconds if Alarm
Yellow ON for 2 seconds if Microwave 
event detected
Green ON for 2 seconds if PIR event 
detected

Microwave Walk Test

Red ON if Microwave is set too high
Green ON if Microwave is set correctly
OFF if Microwave is set too low

 

TROUBLESHOOTING 

RED LED flashing rapidly during normal operation indicates a trouble 
condition.  A microwave, PIR, or temperature compensation fault is 
present, or a communication error has occured.  Supervision errors 
and low battery conditions are indicated at the panel.  

Solution:

  Momentarily power down the sensor by removing and 

replacing all the batteries.  If the trouble does not clear, replace the 
sensor.   
 

SPECIFICATIONS 

Range:

  50’ x 60’ (15 m x 18 m) [installed] 

35’ x 40’ (11 m x 12 m) [included]

 

Batteries:

  Four 1.5V AA Lithium Batteries (Use only Energizer L91) 

Battery Caution: Risk of fire, explosion and burns.  Do not 
recharge, disassemble, heat above 100° C (212° F), or incinerate.  
Dispose of used batteries promptly.  Keep away from children.

 

Microwave Frequency:

  24.125 GHz (K-band)

 

RF Frequency:

  345 MHz 

PIR White Light Immunity:

  6,500 Lux typical 

Fluorescent Light Filter:

  50 Hz or 60 Hz, switch selectable  

Operating Temperature:

  -20° to 55° C  (-4° to 131° F),  

5% - 95% relative humidity (non-condensing) 

Self-Tests:

  

Microwave supervision; End-to-End PIR self-test; Temperature 
Compensation 

Temperature Compensation:

  Advanced Dual Slope 

PIR Fields of View:  

Wide Angle Lens (P/N 5-532-439-01)

 

44 long range zones   

12 intermediate zones 

6 lower zones 

 

4 look-down zones 

Animal Immune Lens (P/N 5-532-489-01)

 

44 long range zones   

36 intermediate zones 

18 lower zones 

 

4 look-down zones 

Dimensions:

  4.93” x 2.93” x 1.68” (12.5cm x 7.5cm x 4.3cm) 

Weight:  

149.0 g (5.26 oz); Packaged:  205.0 g (7.23 oz) 

Accessories:

  

O

ptional Lens Kits -

  

  Long Range Curtain Lens Kit  15 m x 3 m / 50’ x 10’  (P/N DT7000-LRLK) 
  High Security Lens Kit  11 m x 12 m / 35’ x 40’   (P/N DT7000-HSLK) 
  Pet Alley Lens Kit  11 m x 12 m / 35’ x 40’  (P/N DT7000-PALK) 

Mounting Brackets

 – 

  SMB-10 Swivel Mount Bracket (P/N 0-000-110-01) 
  SMB-10C Swivel Mount Ceiling Bracket (P/N 0-000-111-01)  

Approval Listings:

   

FCC 
IC 
CE,    C-Tick,    cULus Listed 

 

 

COMPLIANCE NOTES 

  Sensor must be tested once per year. 

  Sensor must have a clear line-of-sight to protected area. 

 

Summary of Contents for 5898

Page 1: ...h a robust wall anchor ON 2 3 4 1 ON 2 3 4 1 PIR Sensitivity LOW Pulse Count 2 Up to 100 lb 45 kg Animal Immunity FR CA PIR Sensitivity LOW Pulse Count 2 Up to 100 lb 45 kg Animal Immunity SP Amer PIR Sensitivity LOW Pulse Count 2 Up to 100 lb 45 kg Animal Immunity PIR Sensitivity HIGH Pulse Count 1 Up to 50 lb 22 6 kg Animal Immunity FR CA PIR Sensitivity HIGH Pulse Count 1 Up to 50 lb 22 6 kg An...

Page 2: ...ensor If necessary adjust the microwave range pulse count or sensitivity setting For LED activation meaning refer to the LED Indicator table 4 MICROWAVE WALK TEST 10 MINUTES 1 Set the Microwave Walk Test DIP switch to ON or toggle it ON and OFF 2 Set Range Adjustment potentiometer to 25 and replace the cover 3 Walk through the detection area and observe the LED 4 If necessary adjust the potentiome...

Page 3: ...the LED 4 If necessary adjust the potentiometer until desired detection range is obtained For LED activation meaning refer to the LED Indicator table Power Up Trouble or Anti Mask Fast Blinking Red LED Enabled or Disabled Condition Indicator LED Slow Blinking Red will finish within 60 seconds Indicator LEDs Normal Walk Test Red ON for 3 seconds if Alarm Yellow ON for 2 seconds if Microwave event d...

Page 4: ...the LED 4 If necessary adjust the potentiometer until desired detection range is obtained For LED activation meaning refer to the LED Indicator table Power Up Trouble or Anti Mask Fast Blinking Red LED Enabled or Disabled Condition Indicator LED Slow Blinking Red will finish within 60 seconds Indicator LEDs Normal Walk Test Red ON for 3 seconds if Alarm Yellow ON for 2 seconds if Microwave event d...

Page 5: ...e Lens P N 5 532 439 01 Installed Top View VUE DE DESSUS VISTA DESDE ARRIBA 35 11m Animal Immune Lens Animal Immune Lens Animal Immune Lens P N 5 532 489 01 Included Top View VUE DE DESSUS VISTA DESDE ARRIBA LENS MASKING LENS MASKING LENS MASKING 5 532 439 01 TOP 50FT LENS MASKING LENS MASKING LENS MASKING 5 532 489 01 TOP 25 35FT Side View VUE DE COTE VISTA LATERAL Side View VUE DE COTE VISTA LAT...

Page 6: ...reless DUAL TEC Motion Sensor Installation Instructions PRELIMINARY DRAFT 5 18 09 6 LENS CHANGE INSTRUCTIONS LENS CHANGE INSTRUCTIONS LENS CHANGE INSTRUCTIONS LENS CHANGE INSTRUCTIONS LENS CHANGE INSTRUCTIONS ...

Page 7: ...5898 Wireless DUAL TEC Motion Sensor Installation Instructions PRELIMINARY DRAFT 5 18 09 7 ...

Page 8: ...rate this equipment IC NOTICE This Class B digital device complies with the Canadian RSS 210 Cet appareil numérique de la Classe B est conforme à la norme CNR 210 du Canada This Class B digital device complies with RSS 210 of the IC rules Operation is subject to the following two conditions 1 this device may not cause harmful interference and 2 this device must accept any interference received inc...

Reviews: