E-MON CLASS 3400 METER
62-0398—02
4
1.0 INTRODUCTION
The Honeywell E-Mon Class 3400 Meter is a 3-element meter with
communications. The device is used to monitor electric power usage of individual
loads after the utility meter and store kW and kVAR data for automatic meter
reading. The Class 3400 meter is dual protocol capable and provides both RS485
and Ethernet communications. Installation must only be performed by qualified
personnel and in accordance with these instructions and all applicable local and
national electrical codes. Honeywell E-Mon and its representatives assume no
responsibility for damages or injury resulting from the improper installation of
this meter.
Verify the input voltage rating and configuration on the unit panel label to ensure
that it is suitable for the intended electrical service. 3400 meters labeled for 120/
208V service MUST NOT be installed on service feeds of 277/480 volts or 347/
600 and vice versa.
Verify that the E-Mon Class 3400 Meter’s current sensors are sized suitably for
the load to be monitored. Compare the color of the arrows on the current sensors
to the chart below to confirm the correct current sensor is being used.
Meter Labeled:
Works On:
120V
120V, 1 Phase
120/240V
120/240V, 1 Phase
277V
277V, 1 Phase
208V
208V, 3 Phase
240V
240V, 3 Phase
400V
400V, 380V, 415V, 3 Phase
480V
480V, 3 Phase
600V
600V, 3 Phase
Sensor Arrow Color Code
Sensor Rating
Brown
100 A
Red
200 A
Yellow
400 A
Black
800 A
Blue
1600 A
White/Black 3200
A
62-0398-02.fm Page 4 Tuesday, May 8, 2018 10:22 AM