E-MON CLASS 3400 METER
13
62-0398—02
6.0 METER INSTALLATION
6.1 Mounting the E-Mon Class 3400 Meter
Use appropriately sized mounting hardware to fasten the meter enclosure to the
selected mounting surface. The four housing mounting holes are centered 8.75”
H x 4” W for the CL3400.
NOTE:
Meters supplied in plastic NEMA 4X enclosures and NEMA JIC Steel
Enclosures (UL Type 1) enclosures must be installed indoors.
6.2 Main Power Board Connections
1.
Installing a temporary ground for ESD protection:
With all circuits de-energized, connect a temporary protective earth ground
connection for ESD protection. Prior to performing any unit wiring, be sure
to discharge any static on your person.
2.
Installing the E-Mon Class 3400 Meter protective earth ground:
Connect an earth ground wire to the E-Mon Class 3400 Meter protective
earth ground lug with a torque of 7 N-m.
M34684
6-35/64 (166)
6-35/64
(166)
5/8 (16)
7-51/64
(198)
3-17/64 (83)
1-5/8
(41)
3-25/64
(86)
Ø 1-3/32 (28) THROUGH
NEAR SIDE ONLY
62-0398-02.fm Page 13 Tuesday, May 8, 2018 10:22 AM