Commissioning:
1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is EET.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display or
controller (Fig. 2).
6. Check / Set operating parameters - see list
7. Save values - if changed
8. Log the controller on to the network then verify
settings on Genus InTouch panel, Set-up Unit
or DIN Box Display.
9. Faults ?..........See ‘Fault Finding’.
Fault Finding:
Set-up Unit does not reach the first
screen.
•
If the red LED beside the display connector is
ON, then the controller is faulty.
You cannot log the controller on to the
network.
•
There may be a controller with the same name,
already logged on the network.
•
There may be a maximum 32 controllers
already on the network segment.
•
Check on the InTouch panel, P.C. or
Supervisor.
Parameter
DIN
Range/Units
Default
HT(LT)
Dsgn
Act.
Red Cycle Temperature
0
1 to 7 / °C
4 (-22)
Red OT Alarm Temp.
2
7 to 10 / °C
8 (-15)
Red UT Alarm Temp.
1
-3 to 4 / °C
2 (-30)
Yellow Cycle Temperature
3
1 to 7 / °C
1 (-22)
Yellow OT Alarm Temp.
5
7 to 10 / °C
5 (-15)
Yellow UT Alarm Temp.
4
-3 to 4 / °C
-1 (-30)
White Cycle Temperature
6
1 to 7 / °C
8 (-22)
White OT Alarm Temp.
8
7 to 10 / °C
12 (-15)
White UT Alarm Temp.
7
-3 to 4 / °C
4 (-30)
Differential Below
9
0 to 30 / °C
1.5 (2)
Case Type: 0=Red ; 1=Yellow
; 2=White
10
0 to 2
0
Alarm Delay
00:00 to 99:00/Min:Sec
05:00
(10:00)
Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm
12
0 to 3
0
Red Log OT Alarm
14
8 to 10 / °C
8(-15)
Red Log UT Alarm
13
-1 to 4 / °C
2(-25)
Yellow Log OT Alarm
16
5 to 7 / °C
5(-15)
Yellow Log UT Alarm
15
-2 to 1 / °C
0(-25)
White Log OT Alarm
18
12 to 14 / °C
12(-15)
White Log UT Alarm
17
3 to 7 / °C
4(-25)
Air On / Off Weight
11
0 to 100 / %
50
Defrost Start
19
00:00 to 23:59/Hrs:Mins
01:00
Number of Defrosts per Day
20
0 to 8
6
No Defrost Time
21
0 to 25 / Hrs.
7
Gas Defrost Detect
22
0 to 30 / °C
18
Defrost Terminate
Temperature
23
6 to 14 / °C
10 (14)
Defrost Minimum Time
24
00:00 to 99:00/Min:Sec
05:00
Defrost Maximum Time
25
00:00 to 99:00/Min:Sec
24:00
(25:00)
Drain Down Time
26
00:00 to 20:00/Min:Sec
01:30
Defrost Recovery Time
27
00:00 to 99:00/Min:Sec
30:00
Defrost Type: 0=Elect.;
1= 2Gas ; 2= 3Gas
28
0 to 2
0
Defrost Mode: 0=Local ;
1=Remote
29
0 to 1
0
Defrost Hold: 0=Off ; 1=On
30
0 to 1
0
Fans in Defrost: 0=Off ; 1=On
31
0 to 1
1
Hour
32
0 to 23
Minute
33
0 to 59
Day
34
0 to 31
Month
35
0 to 12
Year
36
0 to 99
BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On
37
0 to 2
0
Lights / Blind: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On
38
0 to 3
0
Sunday (Blinds) Up / Down
39/40
00:00 to 23:59/Hrs:Mins
08:00/20:00
Monday Up / Down
41/42
00:00 to 23:59/Hrs:Mins
08:00/20:00
Tuesday Up / Down
43/44
00:00 to 23:59/Hrs:Mins
08:00/20:00
Wednesday Up / Down
45/46
00:00 to 23:59/Hrs:Mins
08:00/20:00
Thursday Up / Down
47/48
00:00 to 23:59/Hrs:Mins
08:00/20:00
Friday Up / Down
49/50
00:00 to 23:59/Hrs:Mins
08:00/20:00
Saturday Up / Down
51/52
00:00 to 23:59/Hrs:Mins
08:00/20:00
Superheat reference
53
8.0 (6.0)
Proportional Gain
54
2.0
Integral Gain
55
Do not change the
2.0
Integral Time
56
value of these
03:00
EEV Size
57
parameters
1.0
Temp. Proportional Gain
58
1.5
Temp. Integral Gain
59
0.7
Temp. Integral Time
60
10:00
Manual Defrost: 0=Off ; 1=On
99
0 to 1
0
EEV004y 7B30FE
Display Alarm Messages:
AL
Temperature alarm
Ft
Probes 1 and 2 are faulty
LA
Log probe alarm
Pn
probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)
EE
EEPROM fault
rr
Internal program fault
En
Plant fault (‘n’ = number)
Store:..................................................
Controller
Name:
Designer:.............................................
Date:...................................................
Engineer:.............................................
Date:...................................................
Comments:
Universal Controller - 3 Range
ZA-10065-EET
Issue a : 14/5/97