Commissioning:

1. Check all electrical connections (Fig. 2).
2. Make sure that the controller software is EET.
3. Check / Set Bit Switches (Fig. 1).
4. Switch the controller ON.
5. Connect Set-up Unit to DIN Box Display or

controller (Fig. 2).

6. Check / Set operating parameters - see list
7. Save values - if changed
8. Log the controller on to the network then verify

settings on Genus InTouch panel, Set-up Unit
or DIN Box Display.

9. Faults  ?..........See ‘Fault Finding’.

Fault Finding:

Set-up Unit does not reach the first
screen.

• 

If the red LED beside the display connector is
ON, then the controller is faulty.

You cannot log the controller on to the
network.

• 

There may be a controller with the same name,
already logged on the network.

• 

There may be a maximum 32 controllers
already on the network segment.

• 

Check on the InTouch panel, P.C. or
Supervisor.

Parameter

DIN

Range/Units

Default
HT(LT)

Dsgn

Act.

Red Cycle Temperature

0

1 to 7 / °C 

4 (-22)

Red OT Alarm Temp.

2

7 to 10 / °C

8 (-15)

Red UT Alarm Temp.

1

-3 to 4 / °C

2 (-30)

Yellow Cycle Temperature

3

1 to 7 / °C

1 (-22)

Yellow OT Alarm Temp.

5

7 to 10 / °C

5 (-15)

Yellow UT Alarm Temp.

4

-3 to 4 / °C

-1 (-30)

White Cycle Temperature

6

1 to 7 / °C 

8 (-22)

White OT Alarm Temp.

8

7 to 10 / °C

12 (-15)

White UT Alarm Temp.

7

-3 to 4 / °C

4 (-30)

Differential Below

9

0 to 30 / °C

1.5 (2)

Case Type: 0=Red ; 1=Yellow
; 2=White

10

0 to 2

0

Alarm Delay

00:00 to 99:00/Min:Sec

05:00

(10:00)

Log Probe Type: 0=Off ;
1=Product ; 2=Alarm ;
3=Prod./Alarm

12

0 to 3

0

Red Log OT Alarm

14

8 to 10 / °C

8(-15)

Red Log UT Alarm

13

-1 to 4 / °C

2(-25)

Yellow Log OT Alarm

16

5 to 7 / °C

5(-15)

Yellow Log UT Alarm

15

-2 to 1 / °C

0(-25)

White Log OT Alarm

18

12 to 14 / °C

12(-15)

White Log UT Alarm

17

3 to 7 / °C

4(-25)

Air On / Off Weight

11

0 to 100 / %

50

Defrost Start

19

00:00 to 23:59/Hrs:Mins

01:00

Number of Defrosts per Day

20

0 to 8

6

No Defrost Time

21

0 to 25 / Hrs.

7

Gas Defrost Detect

22

0 to 30 / °C

18

Defrost Terminate
Temperature

23

6 to 14 / °C

10 (14)

Defrost Minimum Time

24

00:00 to 99:00/Min:Sec

05:00

Defrost Maximum Time

25

00:00 to 99:00/Min:Sec

24:00

(25:00)

Drain Down Time

26

00:00 to 20:00/Min:Sec

01:30

Defrost Recovery Time

27

00:00 to 99:00/Min:Sec

30:00

Defrost Type: 0=Elect.;
1= 2Gas ; 2= 3Gas

28

0 to 2

0

Defrost Mode: 0=Local ;
1=Remote

29

0 to 1

0

Defrost Hold: 0=Off ; 1=On

30

0 to 1

0

Fans in Defrost: 0=Off ; 1=On

31

0 to 1

1

Hour

32

0 to 23

Minute

33

0 to 59

Day

34

0 to 31

Month

35

0 to 12

Year

36

0 to 99

BST / GMT Select: 0=Auto ;
1=Man.Off ; 2=Man.On

37

0 to 2

0

Lights / Blind: 0=Local ;
1=Remote ; 2=Man.Off ;
3=Man.On

38

0 to 3

0

Sunday (Blinds) Up / Down

39/40

00:00 to 23:59/Hrs:Mins

08:00/20:00

Monday Up / Down

41/42

00:00 to 23:59/Hrs:Mins

08:00/20:00

Tuesday Up / Down

43/44

00:00 to 23:59/Hrs:Mins

08:00/20:00

Wednesday Up / Down

45/46

00:00 to 23:59/Hrs:Mins

08:00/20:00

Thursday Up / Down

47/48

00:00 to 23:59/Hrs:Mins

08:00/20:00

Friday Up / Down

49/50

00:00 to 23:59/Hrs:Mins

08:00/20:00

Saturday Up / Down

51/52

00:00 to 23:59/Hrs:Mins

08:00/20:00

Superheat reference

53

8.0 (6.0)

Proportional Gain

54

2.0

Integral Gain

55

Do not change the

2.0

Integral Time

56

value of these

03:00

EEV Size

57

parameters

1.0

Temp. Proportional Gain

58

1.5

Temp. Integral Gain

59

0.7

Temp. Integral Time

60

10:00

Manual Defrost: 0=Off ; 1=On

99

0 to 1

0

EEV004y   7B30FE

Display Alarm Messages:

AL

Temperature alarm

Ft

Probes 1 and 2 are faulty

LA

Log probe alarm

Pn

probe ‘n’ faulty or not connected
(Where ‘n’ = probe number)

EE

EEPROM fault

rr

Internal program fault

En

Plant fault (‘n’ = number)

Store:..................................................

Controller
Name:

Designer:.............................................

Date:...................................................

Engineer:.............................................

Date:...................................................

Comments:

Universal Controller - 3 Range
ZA-10065-EET
Issue a : 14/5/97

Summary of Contents for 190887-EET

Page 1: ...ll Control Systems All Rights Reserved ZA10063 EET UK07 R00597 ZA10064 EET UK07 R00597 ZA10065 EET UK07 R00597 ZA10066 EET UK07 R00597 ZA10067 EET UK07 R00597 ZA10068 EET UK07 R00597 190887 EET TUSCAN EEV CONTROLLER INSTALLATION GUIDE ...

Page 2: ...e of this product or document All Installation and Commissioning work on Honeywell Elm equipment should be carried out by suitably qualified personnel only Normal safety precautions and good working practice should be observed to prevent damage or injury at all times We welcome comments about our products and documentation Contact us at Honeywell Elm Cooling Refrigeration Newhouse Industrial Estat...

Page 3: ...Esc Alarm Network Defrost DIN Box Display with Keyswitch OR white green Plant fault ZA 10063 EET Issue a 14 5 97 Product Part No Universal Controller with Elm probes 190887 Universal Controller with PT 1000 probes 191126 Warning Before you work on this equipment isolate the electrical supply and also the live feed to any incoming signals Remember that live signals may be derived from more than one...

Page 4: ...0 00 to 99 00 Min Sec 30 00 Defrost Type 0 Elect 1 2Gas 2 3Gas 15 0 to 2 0 Defrost Mode 0 Local 1 Remote 16 0 to 1 0 Defrost Hold 0 Off 1 On 17 0 to 1 0 Fans in Defrost 0 Off 1 On 18 0 to 1 1 Hour 19 0 to 23 Minute 20 0 to 59 Day 21 0 to 31 Month 22 0 to 12 Year 23 0 to 99 BST GMT Select 0 Auto 1 Man Off 2 Man On 24 0 to 2 0 Lights Blind 0 Local 1 Remote 2 Man Off 3 Man On 25 0 to 3 0 Sunday Blind...

Page 5: ...work Defrost OR white green Plant fault DIN Box Display DIN Box Display with Keyswitch Bit Switch Settings Fig 1 Shaded area Switch Position Off On Genus network 1 Alternative network Elm Probes controller part no 190887 2 PT 1000 Probes controller part no 191126 Relay 5 Remote 3 Relay 5 Switches Alarm DIN Display Buttons Active 4 DIN Display Buttons Inactive 5 Coldroom option 6 7 LT Range Frozen ...

Page 6: ...r of Defrosts per Day 10 0 to 8 6 No Defrost Time 11 0 to 25 Hrs 7 Gas Defrost Detect 12 0 to 30 C 18 Defrost Terminate Temperature 13 49 to 30 C 10 14 Defrost Minimum Time 14 00 00 to 99 00 Min Sec 05 00 Defrost Maximum Time 15 00 00 to 99 00 Min Sec 24 00 25 00 Drain Down Time 16 00 00 to 20 00 Min Sec 01 30 Defrost Recovery Time 17 00 00 to 99 00 Min Sec 30 00 Defrost Type 0 Elect 1 2Gas 2 3Gas...

Page 7: ...e Setup unit extension cable screen red white black green blue green yellow white red CN7 CN8 P2 P1 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN5 CN6 CN4 CN3 CN2 CN1 EET Controller on a Genus Network screen white black CN7 Controller on a Woodley Network Controller Fig 2 Position of probes should be in accordance with case manufacturers instructions 10k 5k If gas defrost is required connect N C S G V to R...

Page 8: ...o 100 50 Defrost Start 19 00 00 to 23 59 Hrs Mins 01 00 Number of Defrosts per Day 20 0 to 8 6 No Defrost Time 21 0 to 25 Hrs 7 Gas Defrost Detect 22 0 to 30 C 18 Defrost Terminate Temperature 23 6 to 14 C 10 14 Defrost Minimum Time 24 00 00 to 99 00 Min Sec 05 00 Defrost Maximum Time 25 00 00 to 99 00 Min Sec 24 00 25 00 Drain Down Time 26 00 00 to 20 00 Min Sec 01 30 Defrost Recovery Time 27 00 ...

Page 9: ...e red CN7 CN8 P2 P1 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN5 CN6 CN4 CN3 CN2 CN1 EET Controller on a Genus Network screen white black CN7 Controller on a Woodley Network Controller Fig 2 Position of probes should be in accordance with case manufacturers instructions 10k 5k 1 5 Ent Esc Alarm Network Defrost DIN Box Display Setup unit extension cable 1 5 Ent Esc Alarm Network Defrost DIN Box Display wi...

Page 10: ...rost Type 0 Elect 1 2Gas 2 3Gas 15 0 to 2 0 Defrost Mode 0 Local 1 Remote 16 0 to 1 0 Defrost Hold 0 Off 1 On 17 0 to 1 0 Fans in Defrost 0 Off 1 On 18 0 to 1 1 Hour 19 0 to 23 Minute 20 0 to 59 Day 21 0 to 31 Month 22 0 to 12 Year 23 0 to 99 BST GMT Select 0 Auto 1 Man Off 2 Man On 24 0 to 2 0 Lights Blind 0 Local 1 Remote 2 Man Off 3 Man On 25 0 to 3 0 Sunday Lights Blinds On Up 26 00 00 to 23 5...

Page 11: ...ectronic expansion valve Setup unit extension cable screen red white black green blue green yellow white red CN7 CN8 P2 P1 CN9 CN10 CN11 CN12 CN13 CN14 CN15 CN5 CN6 CN4 CN3 CN2 CN1 EET Controller on a Genus Network screen white black CN7 Controller on a Woodley Network Controller Fig 2 Position of probes should be in accordance with case manufacturers instructions 10k 5k Connection to valve driver...

Page 12: ... 0 to 99 BST GMT Select 0 Auto 1 Man Off 2 Man On 23 0 to 2 0 Lights Blind 0 Local 1 Remote 2 Man Off 3 Man On 24 0 to 3 0 Sunday Blinds Up Down 25 26 00 00 to 23 59 Hrs Mins 08 00 20 00 Monday Up Down 27 28 00 00 to 23 59 Hrs Mins 08 00 20 00 Tuesday Up Down 29 30 00 00 to 23 59 Hrs Mins 08 00 20 00 Wednesday Up Down 31 32 00 00 to 23 59 Hrs Mins 08 00 20 00 Thursday Up Down 33 34 00 00 to 23 59 ...

Page 13: ...Fig 2 Defrost Door open Closed Position of probes should be in accordance with coil manufacturers instructions 5k Connection to valve driver board If gas defrost is required connect N C S G V to Relay 3 N C contact P5 Defrost terminate Bit Switch Settings Fig 1 Shaded area Switch Position Off On Genus network 1 Alternative network Elm Probes controller part no 190887 2 PT 1000 Probes controller pa...

Page 14: ...7 0 to 2 0 Defrost Mode 0 Local 1 Remote 18 0 to 1 0 Defrost Hold 0 Off 1 On 19 0 to 1 0 Hour 20 0 to 23 Minute 21 0 to 59 Day 22 0 to 31 Month 23 0 to 12 Year 24 0 to 99 BST GMT Select 0 Auto 1 Man Off 2 Man On 25 0 to 2 0 Door Alarm Delay 26 00 00 to 99 00 Min Sec 20 00 Drip Pan Heater 0 Off 1 On 27 0 to 1 0 Fans Off when Door is Open 0 Off 1 On 28 0 to 1 0 Liquid Line Closed when Door is Open 0...

Reviews: