F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER

68-0198EF-2

4

IMPORTANT

Never hang the air cleaner higher than 16 ft (5m) 

above the floor.

INSTALLATION

WARNING

Explosion Hazard Possible.

Can cause personal injury or equipment damage.

Do not install or use the F111 (series 11000) air 

cleaner where there is any danger of gas, vapor or 

dust explosion.

IMPORTANT

This air cleaner has not been investigated for use in 

the ceilings of fire-resistant assemblies.

CAUTION

Electrical Hazard.

Can cause personal injury or equipment damage.

Turn off power before installing or servicing the air 

cleaner.

IMPORTANT

Stand on a stable platform when working with the air 

cleaner.

When Installing this Product…

1.

Read these instructions carefully. Failure to follow them 

could damage the product or cause a hazardous condi-

tion.

2.

Check the ratings given in the instructions and on the 

product to make sure the product is suitable for your 

application.

3.

Installer must be a trained, experienced service techni-

cian.

4.

After installation is complete, check out product opera-

tion as provided in these instructions.

Unpack the Air Cleaner

Check that all components are included. The unit consists of:

• cabinet and grille/door assembly,

• media modules,

• literature.

Make Opening (if Mounting in a Drop Ceiling)

1.

Size the opening to fit the air cleaner cabinet as closely 

as possible. 

2.

Frame the opening to provide adequate support for the 

cabinet. The cabinet must fit snugly in the opening; 

allow no more than 1/4 in. (6 mm) from the opening to 

each side of the cabinet.

3.

Cover the framing and any unused portion of the open-

ing with wallboard, plywood, or other material and finish 

to match the ceiling.

Electrical Hookup

All wiring must comply with applicable codes and ordinances. 

The power source must agree with the model type: 120V, 

60 Hz; 208/230V, 50/60 Hz or 277V, 60 Hz. The air cleaners 

are internally prewired.

1.

Locate the prepunched hole in the side of the cabinet.

2.

Remove the air cleaner lid.

3.

Remove the connection box cover plate in the center 

cavity of the air cleaner.

4.

Refer to Fig. 3 and 4 for typical wiring diagrams.

WARNING

Risk of Fire or Electric Shock.

Can cause personal injury or equipment damage.

Use only Honeywell 32000234 (41105) Variable Speed 

Switch (accessory) to regulate air cleaner speed. 

Using a different speed controller may void the 

warranty.

IMPORTANT

• Be sure the air cleaner is grounded for correct

operation and safety.

• Canadian installation: NEVER install in ceilings with 

thermal insulation value greater than R-40.

Fig. 3. Typical F111 (series 11000) 120V, 60 Hz or 

208/230, 50/60 Hz wiring diagram.

Fig. 4.  Typical F111 (series 11000) 277V, 

60 Hz wiring diagram.

Mount Air Cleaner Cabinet

The air cleaner can be mounted in a drop ceiling system or 

hung in an open area. Both mounting methods require the air 

cleaner to be level and positioned facing downward for correct 

operation.

1.

Remove the door/grille from the carton and set it aside. 

2.

Fit the cabinet into the prepared ceiling opening or 

position on the ceiling.

M12657

CAPACITOR

WHITE
GREEN

BLACK

FACTORY WIRING

BROWN

EXTERNAL
WIRING BY
INSTALLER

MOTOR

M11748

CAPACITOR

PURPLE
GREEN

BLACK

FACTORY WIRING

BROWN

EXTERNAL
WIRING BY
INSTALLER

BROWN 
STRIPE

MOTOR
277 V

Summary of Contents for 11000 Series

Page 1: ...moke from the air circulated through the filter FEATURES High Efficiency Particulate Air HEPA filter models are 99 97 efficient and the hospital grade particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger There is also a 95 ASHRAE model Circulates up to 1230 cfm Designed to overcome the increase in air flow resistance normall...

Page 2: ...may not exactly match the listed specifica tions Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models Refer to Table 1 for model descriptions Color White cabinet and cover Blower Motor Single speed direct drive forward curve Dimensions See Fig 1 for dimensions Table 1 F111 Ser...

Page 3: ...tributor or local Honeywell Commercial Air Cleaner Distributor Table 3 Determining the Minimum Number of Air Cleaners Needed for a Space Choose Location Choosing the correct location for the air cleaner affects the overall performance of the unit The bidirectional airflow pattern must flow into the longest reaches of the zone being cleaned See Fig 2 Fig 2 Correct positioning of the air cleaner for...

Page 4: ... to each side of the cabinet 3 Cover the framing and any unused portion of the open ing with wallboard plywood or other material and finish to match the ceiling Electrical Hookup All wiring must comply with applicable codes and ordinances The power source must agree with the model type 120V 60 Hz 208 230V 50 60 Hz or 277V 60 Hz The air cleaners are internally prewired 1 Locate the prepunched hole ...

Page 5: ...ure the fastener tabs are facing downward and fas ten them 10 Install the prefilter in the air cleaner lid Position the metal screen mesh so it is facing upward when the lid is closed Lid Assembly The F111 lid is held in place by two separable hinges and two spring loaded plungers To install the spring loaded plungers on the lid follow these steps 1 Pull the plunger back and twist a quarter turn t...

Page 6: ...minimum ventilation rates to dilute air contamination in specific applications The ventilation rates usually assume the injection of outdoor air measured as air exchange rate The use of the F111 series 11000 air cleaner to comply with ventilation requirements is an acceptable alternative to ventilation with outdoor air However at least 20 of a specified ventilation rate or code must be derived fro...

Page 7: ...bents emit a continuous strong pungent odor If the air cleaner is turned off for 8 to 10 hours there will a temporary odor when it is turned back on If the odor persists for 30 minutes it is time to replace the filters NOTE When tobacco smoke is a contaminant both the particle filter and the adsorbent filter will need to be serviced at the same time 1 Slowly open the lid supporting the lid so the ...

Page 8: ...r 277V 60 Hz 1 32000550 810160 4 Motor 120 V 60 Hz 1 32000270 810208 Motor 208 230V 50 60 Hz 1 32000263 810158 Motor 277V 60 Hz 1 32000264 810159 5 99 97 HEPA media filter 1 32000204 21002 95 hospital grade filter 1 32000203 21001 6 Prefilter disposable 1 32002307 810134 7 Lid assembly without hinges and latches 1 32002308 810198 OPTIONAL Parts not shown in Fig 8 Speed switch variable 1 32000234 4...

Page 9: ...2307 HEPA MEDIA FILTER PART 32000204 95 ASHRAE PARTICLE FILTER PART 50004759 001 MOTOR 120V 60 HZ PART 32000270 208 230V 50 60 HZ PART 32000263 277V 60 HZ PART 32000264 MOTOR CAPACITOR 120V 60 HZ PART 32000265 208 230V 50 60 HZ PART 32000549 277V 60 HZ PART 32000550 BLOWER WHEEL PART 32002285 SORBENT MEDIA MODULE 2 REQUIRED CPZ PART 32004078 001 CHARCOAL PART 32004078 002 ZEOLITE PART 32004078 003...

Page 10: ... LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PROD UCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND HONEYWELL INC EXPRESSL...

Page 11: ...llen et une partie de la fumée provenant de la cuisson des aliments CARACTÉRISTIQUES Les modèles à filtre absolu HEPA ont une efficacité de 99 97 et les modèles à filtre de classe de qualité hôpital ont une efficacité de 95 lorsqu ils retiennent les particules de 0 3 micron Les deux modèles retiennent les particules plus grosses et plus petites avec plus d efficacité Diffusion d air d environ 1230...

Page 12: ...ation ne comprennent pas les tolérances normales de fabrication Par conséquent il se peut que l appareil ne corresponde pas exactement aux caractéristiques indiquées De même le produit a été mis à l essai et étalonné dans des conditions entièrement contrôlées et on peut s attendre à de légères différences de fonctionnement si ces conditions sont modifiées Tableau 1 Description du filtre F111 série...

Page 13: ...eau 3 Nombre de filtres à air requis en général par volume Choix d un emplacement Le choix d un bon emplacement pour le filtre à air a une incidence sur le rendement de l appareil Ainsi l écoulement d air dans les deux directions doit aller dans le sens dont la portée est la plus longue dans l espace à filtrer Voir la Fig 2 Fig 2 Positionnement adéquat du filtre à air pour un filtrage optimal Le f...

Page 14: ...e partie inutilisée de l ouver ture d un panneau de revêtement ou de contre plaqué ou d un autre matériau et finir de façon à ce que le cadre s harmonise au plafond Raccordement électrique Tout le câblage électrique doit être conforme aux codes et aux règlements locaux La source d alimentation doit convenir au type de modèle 120V 60 Hz 208 230V 50 60 Hz ou 277V 60 Hz Les filtres à air sont pré câb...

Page 15: ... le manipuler par le cadre seulement sinon l élément filtrant risque d être endommagé 9 Retirer les modules de sorbant CPZMC selon le modèle de leur emballage et installer un module dans chaque cavité S assurer que les languettes de fixation pointent vers le bas et les fixer en place 10 Installer le préfiltre dans le couvercle du filtre à air Placer le filtre de métal de façon à ce qu il pointe ve...

Page 16: ...saires Les facteurs qui déterminent le rythme des renouvellements d air sont les suivants rythme de production des diverses matières polluantes taux de concentration des polluants réduction souhaitée de la pollution Il y aura toujours des particules polluantes dans l air dans les endroits où la pollution se produit Les systèmes de filtrage de l air et les ventilateurs n éliminent pas les particule...

Page 17: ...on plus forte MISE EN GARDE Il ne faut pas toucher l élément filtrant à plis Il faut le manipuler par le cadre seulement sinon l élément filtrant risque d être endommagé 7 Refermer le couvercle et fixer les attaches Module de sorbant CPZMC Le module de sorbant CPZMC sert à retenir les gaz les vapeurs les odeurs et les composés organiques volatils COV contenus dans l air qui passe à travers le filt...

Page 18: ...77 V 60 Hz 1 32000550 810160 4 Moteur 120V 60 Hz 1 32000270 810208 Moteur 208 230V 50 60 Hz 1 32000263 810158 Moteur 277V 60 Hz 1 32000264 810159 5 Filtre HEPA à élément filtrant 99 9 1 32000204 21002 Filtre à particules de classe de qualité hôpital 95 1 32000203 21001 6 Préfiltre jetable 1 32002307 810134 7 Couvercle sans charnières ni loquet 1 32002308 810198 PIÈCES FACULTATIVES Pièces non illus...

Page 19: ...PA 32000204 FILTRE ASHRAE 95 À PARTICULES 50004759 001 MOTEUR 120V 60HZ 32000270 208 230V 50 60HZ 32000263 277V 60HZ 32000264 CONDENSATEUR DE MOTEUR 120V 60HZ 32000265 208 230V 50 60HZ 32000549 277V 60HZ 32000550 ROTOR DE VENTILATEUR 320002285 MODULE DE SORBANT CPZMC IL EN FAUT 2 32004078 001 MODULE DE CHARBON IL EN FAUT 2 32004078 002 MODULE DE ZÉOLITE IL EN FAUT 2 32004078 003 MODULE DE PERMANGA...

Page 20: ...NASSUME AUCUNE RESPONSABILITÉ POUR QUELQUE DOMMAGE OU PERTE QUE CE SOIT INDIRECT OU ACCESSOIRE RÉSULTANT DIRECTEMENT OU INDIRECTEMENT DUNE VIOLATION QUELCONQUE DUNE GARANTIE EXPRESSE OU TACITE APPLICABLE AU PRÉSENT PRODUIT OU POUR TOUTE AUTRE DÉFECTUOSITÉ DU PRÉSENT PRODUIT Certains États territoires ou provinces ne permettent pas l exclusion ou la restriction des dommages indirects et par conséqu...

Reviews: