F111 (SERIES 11000) IN CEILING MEDIA AIR CLEANER

68-0198EF-2

6

Removing /Replacing the Lid

IMPORTANT

The lid is heavy. Make sure that it is supported 

before removing.

To remove the lid, swing it into the open position. Move the lid 

to the side to disengage the hinge pins. Reverse the 

procedure to replace the lid.

OPERATION

The F111 (series 11000) in Ceiling Media Air Cleaner has 

been engineered to improve indoor air quality for commercial 

and industrial applications. The filters are the most practical 

and effective filtering system for removing atmospheric dust, 

pollens, bacteria, viruses, mold spores, smoke, fumes, mists 

and aerosols. Refer to Fig. 7.

Fig. 7. F111 (series 11000) air cleaner operation.

The air cleaner is either operating (power on) or off (power 

off). There are no other operational options available. Even 

when the area is unoccupied, the air cleaner can be operated 

continuously to prevent buildup of airborne contaminants. 

Operate the air cleaner only when the area is occupied when 

specific activities produce contaminants.

The CPZ™ sorbent module has the ability to collect and hold 

gas-phase compounds and vapors typically found in 

commercial and light industrial facilities. These gases and 

vapors frequently appear as odors that, at times, can be 

annoying and irritating. The modules become saturated after 

collecting 25% to 50% of their weight in gaseous odors. The 

quantity of CPZ™ material provides adequate dwell time to 

ensure up to 95% collection efficiency in the first pass. This 

also provides a long maintenance-free service life.

The minimum recommended air exchange rate is 2.5 times 

per hour. In a heavily contaminated area, up to 15 air 

exchanges per hour can be necessary. The factors that 

determine what the rate of air exchange should be are:

• generation rates of the various pollutants;

• concentration level of the pollutants;

• desired contamination reduction level.

Airborne contaminants will always be present in the air where 

contaminant generations take place. Air cleaning systems and 

ventilators do not eliminate airborne contaminants, they 

reduce the excessive accumulation of the contaminants. To 

eliminate the contamination, the source of contamination must 

be removed.

Local, Federal and professional ventilation engineering 

standards and codes prescribe minimum ventilation rates to 

dilute air contamination in specific applications. The 

ventilation rates usually assume the injection of outdoor air 

measured as air exchange rate. The use of the F111 (series 

11000) air cleaner to comply with ventilation requirements is 

an acceptable alternative to ventilation with outdoor air. 

However, at least 20% of a specified ventilation rate or code 

must be derived from outdoor air. The F111 (series 11000) air 

cleaner filtered and recirculated air can be the remaining 80%.

SERVICE

CAUTION

Electrical Hazard.

Can cause personal injury or equipment damage.

Turn off power before installing or servicing the air 

cleaner.

IMPORTANT

Be sure to change filters as recommended to prevent 

reduced airflow in the air cleaner.Stand on a stable 

platform when working with the air cleaner.

The useful life of the CPZ™ sorbent modules may vary from 4 

to 24 months, depending on the application. In most 

applications, the sorbent media life ranges from 12 to 18 

months. The particle filter life ranges from 6 to 24 months with 

12 to 24 months as an average. The modules and filters need 

to be changed more frequently in facilities that operate 24 

hours a day. 

Prefilter

The disposable prefilter collects large dust particulates and 

lint- type airborne fibers. Check the filter every two weeks to 

determine the replacement frequency:

1.

Slowly open the lid, supporting the lid so the filters do 

not fall out.

2.

Remove the dirty prefilter.

3.

Install the new prefilter in the air cleaner lid. Position the 

metal screen mesh so it is facing upward when the lid is 

closed.

4.

Close and latch the lid.

Particle Filter

The particle filter collects particulates that pass through the 

prefilter. The filter life is typically from 1 to 2 years. There is 

decreased air quality and a pulsing sound when the filter is 

loading the contaminants. The filter must be replaced when 

the pulsing sound is noticed.

NOTE: The filter must be replaced. Washing, vacuuming or 

reverse air blasting does not clean it.

1.

Slowly open lid, supporting it so the filters do not fall out.

2.

Open the securing strips and with both hands and slide 

the filter toward you.

3.

Place spent filter in a plastic trash bag and dispose of 

properly.

4.

Inspect the motor brackets for loose fasteners and 

tighten as necessary.

M12651A

CEILING LINE

CLEAN AIR
DISCHARGE

CEILING LINE

CLEAN AIR
DISCHARGE

PARTICLE FILTER

PREFILTER

AIR IN

AIR IN

INTAKE

BLOWER

MOTOR

AIR VENTS

CPZ™
SORBENT 
FILTER
MODULE

CPZ™
SORBENT 
FILTER
MODULE

Summary of Contents for 11000 Series

Page 1: ...moke from the air circulated through the filter FEATURES High Efficiency Particulate Air HEPA filter models are 99 97 efficient and the hospital grade particle filter models are 95 efficient at 0 3 micron particles Both models are more efficient on particles smaller and larger There is also a 95 ASHRAE model Circulates up to 1230 cfm Designed to overcome the increase in air flow resistance normall...

Page 2: ...may not exactly match the listed specifica tions Also this product is tested and calibrated under closely controlled conditions and some minor differences in performance can be expected if those conditions are changed Models Refer to Table 1 for model descriptions Color White cabinet and cover Blower Motor Single speed direct drive forward curve Dimensions See Fig 1 for dimensions Table 1 F111 Ser...

Page 3: ...tributor or local Honeywell Commercial Air Cleaner Distributor Table 3 Determining the Minimum Number of Air Cleaners Needed for a Space Choose Location Choosing the correct location for the air cleaner affects the overall performance of the unit The bidirectional airflow pattern must flow into the longest reaches of the zone being cleaned See Fig 2 Fig 2 Correct positioning of the air cleaner for...

Page 4: ... to each side of the cabinet 3 Cover the framing and any unused portion of the open ing with wallboard plywood or other material and finish to match the ceiling Electrical Hookup All wiring must comply with applicable codes and ordinances The power source must agree with the model type 120V 60 Hz 208 230V 50 60 Hz or 277V 60 Hz The air cleaners are internally prewired 1 Locate the prepunched hole ...

Page 5: ...ure the fastener tabs are facing downward and fas ten them 10 Install the prefilter in the air cleaner lid Position the metal screen mesh so it is facing upward when the lid is closed Lid Assembly The F111 lid is held in place by two separable hinges and two spring loaded plungers To install the spring loaded plungers on the lid follow these steps 1 Pull the plunger back and twist a quarter turn t...

Page 6: ...minimum ventilation rates to dilute air contamination in specific applications The ventilation rates usually assume the injection of outdoor air measured as air exchange rate The use of the F111 series 11000 air cleaner to comply with ventilation requirements is an acceptable alternative to ventilation with outdoor air However at least 20 of a specified ventilation rate or code must be derived fro...

Page 7: ...bents emit a continuous strong pungent odor If the air cleaner is turned off for 8 to 10 hours there will a temporary odor when it is turned back on If the odor persists for 30 minutes it is time to replace the filters NOTE When tobacco smoke is a contaminant both the particle filter and the adsorbent filter will need to be serviced at the same time 1 Slowly open the lid supporting the lid so the ...

Page 8: ...r 277V 60 Hz 1 32000550 810160 4 Motor 120 V 60 Hz 1 32000270 810208 Motor 208 230V 50 60 Hz 1 32000263 810158 Motor 277V 60 Hz 1 32000264 810159 5 99 97 HEPA media filter 1 32000204 21002 95 hospital grade filter 1 32000203 21001 6 Prefilter disposable 1 32002307 810134 7 Lid assembly without hinges and latches 1 32002308 810198 OPTIONAL Parts not shown in Fig 8 Speed switch variable 1 32000234 4...

Page 9: ...2307 HEPA MEDIA FILTER PART 32000204 95 ASHRAE PARTICLE FILTER PART 50004759 001 MOTOR 120V 60 HZ PART 32000270 208 230V 50 60 HZ PART 32000263 277V 60 HZ PART 32000264 MOTOR CAPACITOR 120V 60 HZ PART 32000265 208 230V 50 60 HZ PART 32000549 277V 60 HZ PART 32000550 BLOWER WHEEL PART 32002285 SORBENT MEDIA MODULE 2 REQUIRED CPZ PART 32004078 001 CHARCOAL PART 32004078 002 ZEOLITE PART 32004078 003...

Page 10: ... LOSS OR DAMAGE OF ANY KIND INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL DAMAGES RESULTING DIRECTLY OR INDIRECTLY FROM ANY BREACH OF WARRANTY EXPRESS OR IMPLIED OR ANY OTHER FAILURE OF THIS PROD UCT Some states do not allow the exclusion or limitation of incidental or consequential damages so this limitation may not apply to you THE WARRANTIES SET FORTH HEREIN ARE EXCLUSIVE AND HONEYWELL INC EXPRESSL...

Page 11: ...llen et une partie de la fumée provenant de la cuisson des aliments CARACTÉRISTIQUES Les modèles à filtre absolu HEPA ont une efficacité de 99 97 et les modèles à filtre de classe de qualité hôpital ont une efficacité de 95 lorsqu ils retiennent les particules de 0 3 micron Les deux modèles retiennent les particules plus grosses et plus petites avec plus d efficacité Diffusion d air d environ 1230...

Page 12: ...ation ne comprennent pas les tolérances normales de fabrication Par conséquent il se peut que l appareil ne corresponde pas exactement aux caractéristiques indiquées De même le produit a été mis à l essai et étalonné dans des conditions entièrement contrôlées et on peut s attendre à de légères différences de fonctionnement si ces conditions sont modifiées Tableau 1 Description du filtre F111 série...

Page 13: ...eau 3 Nombre de filtres à air requis en général par volume Choix d un emplacement Le choix d un bon emplacement pour le filtre à air a une incidence sur le rendement de l appareil Ainsi l écoulement d air dans les deux directions doit aller dans le sens dont la portée est la plus longue dans l espace à filtrer Voir la Fig 2 Fig 2 Positionnement adéquat du filtre à air pour un filtrage optimal Le f...

Page 14: ...e partie inutilisée de l ouver ture d un panneau de revêtement ou de contre plaqué ou d un autre matériau et finir de façon à ce que le cadre s harmonise au plafond Raccordement électrique Tout le câblage électrique doit être conforme aux codes et aux règlements locaux La source d alimentation doit convenir au type de modèle 120V 60 Hz 208 230V 50 60 Hz ou 277V 60 Hz Les filtres à air sont pré câb...

Page 15: ... le manipuler par le cadre seulement sinon l élément filtrant risque d être endommagé 9 Retirer les modules de sorbant CPZMC selon le modèle de leur emballage et installer un module dans chaque cavité S assurer que les languettes de fixation pointent vers le bas et les fixer en place 10 Installer le préfiltre dans le couvercle du filtre à air Placer le filtre de métal de façon à ce qu il pointe ve...

Page 16: ...saires Les facteurs qui déterminent le rythme des renouvellements d air sont les suivants rythme de production des diverses matières polluantes taux de concentration des polluants réduction souhaitée de la pollution Il y aura toujours des particules polluantes dans l air dans les endroits où la pollution se produit Les systèmes de filtrage de l air et les ventilateurs n éliminent pas les particule...

Page 17: ...on plus forte MISE EN GARDE Il ne faut pas toucher l élément filtrant à plis Il faut le manipuler par le cadre seulement sinon l élément filtrant risque d être endommagé 7 Refermer le couvercle et fixer les attaches Module de sorbant CPZMC Le module de sorbant CPZMC sert à retenir les gaz les vapeurs les odeurs et les composés organiques volatils COV contenus dans l air qui passe à travers le filt...

Page 18: ...77 V 60 Hz 1 32000550 810160 4 Moteur 120V 60 Hz 1 32000270 810208 Moteur 208 230V 50 60 Hz 1 32000263 810158 Moteur 277V 60 Hz 1 32000264 810159 5 Filtre HEPA à élément filtrant 99 9 1 32000204 21002 Filtre à particules de classe de qualité hôpital 95 1 32000203 21001 6 Préfiltre jetable 1 32002307 810134 7 Couvercle sans charnières ni loquet 1 32002308 810198 PIÈCES FACULTATIVES Pièces non illus...

Page 19: ...PA 32000204 FILTRE ASHRAE 95 À PARTICULES 50004759 001 MOTEUR 120V 60HZ 32000270 208 230V 50 60HZ 32000263 277V 60HZ 32000264 CONDENSATEUR DE MOTEUR 120V 60HZ 32000265 208 230V 50 60HZ 32000549 277V 60HZ 32000550 ROTOR DE VENTILATEUR 320002285 MODULE DE SORBANT CPZMC IL EN FAUT 2 32004078 001 MODULE DE CHARBON IL EN FAUT 2 32004078 002 MODULE DE ZÉOLITE IL EN FAUT 2 32004078 003 MODULE DE PERMANGA...

Page 20: ...NASSUME AUCUNE RESPONSABILITÉ POUR QUELQUE DOMMAGE OU PERTE QUE CE SOIT INDIRECT OU ACCESSOIRE RÉSULTANT DIRECTEMENT OU INDIRECTEMENT DUNE VIOLATION QUELCONQUE DUNE GARANTIE EXPRESSE OU TACITE APPLICABLE AU PRÉSENT PRODUIT OU POUR TOUTE AUTRE DÉFECTUOSITÉ DU PRÉSENT PRODUIT Certains États territoires ou provinces ne permettent pas l exclusion ou la restriction des dommages indirects et par conséqu...

Reviews: