background image

VR9205R SERIES 1000 DIRECT IGNITION GAS CONTROL WITH INTEGRATED GAS/AIR MODULE

69-2305—03

4

Complete the instructions below for installing the piping, 
installing the control, connecting the wiring. Make sure the 
leak test you perform on the control after completing the 
installation includes leak testing the bushings.

Location

The gas controls are mounted in the appliance vestibule 
on the gas manifold. If this is a replacement application, 
mount the gas control in the same location as the old 
control.

Locate the combination gas control where it cannot be 
affected by steam cleaning, high humidity, or dripping 
water, corrosive chemicals, dust or grease accumulation 
or excessive heat. 

To assure proper operation, follow these guidelines:

• Locate gas control in a well-ventilated area.
• Mount gas control high enough above cabinet bottom 

to avoid exposure to flooding or splashing water.

• Assure the ambient temperature does not exceed the 

ambient temperature ratings for each component.

• Cover gas control if appliance is cleaned with water, 

steam, or chemicals or to avoid dust and grease 
accumulation.

• Avoid locating gas control where exposure to corrosive 

chemical fumes or dripping water are likely.

Install Piping to Control

All piping must comply with local codes and ordinances or 
with the National Fuel Gas Code (ANSI Z223.1, 
NFPA No. 54), whichever applies. Tubing installation must 
comply with approved standards and practices.

1.

Use new, properly reamed pipe that is free from 
chips. If tubing is used, make sure the ends are 
square, deburred and clean. All tubing bends must 
be smooth and without deformation.

2.

Run pipe or tubing to the control. If tubing is used, 
obtain a tube-to-pipe coupling to connect the tubing 
to the control.

3.

Install a sediment trap in the supply line to the 
control. See Fig. 3.

Install Control

1.

Mount with the coils 90 degrees from the vertical 
upright position.

2.

Mount so the gas flow is in the direction of the arrow 
on the bottom of the control.

3.

Thread the pipe the amount shown in Table 3 for 
insertion into control or adapters. Do not thread 
pipe too far. Valve distortion or malfunction can 
result if the pipe is inserted too deeply.

4.

Apply a moderate amount of good quality pipe 
compound (do not use Teflon tape) only to the pipe, 
leaving two end threads bare. On LP installations, 
use a compound resistant to LP gas. See Fig. 4.

5.

Remove the seals over the control inlet and outlet 
before installing pipe.

6.

Connect the pipe to the control inlet and outlet. Use 
a wrench on the square end or a socket on the hex 
end of the control. See Fig. 5.

a

All dimensions are in inches.

b

OK when bushings are used.

Air pressure connections

The air pressure difference must be connected to the two 
air pressure connections. See Fig. 1.

Fig. 3.  Sediment trap installation.

Fig. 4. Use moderate amount of pipe compound.

Table 3. NPT Pipe Thread Length.

a

Pipe Size

Thread Pipe 

This Amount

Maximum Depth Pipe can 

be Inserted into Control

3/8

b

9/16

3/8

1/2

3/4

1/2

GAS

CONTROL

GAS

CONTROL

HORIZONTAL

DROP

PIPED

GAS

SUPPLY

PIPED

GAS

SUPPLY

3 IN.

(76 MM)

MINIMUM

3 IN.

(76 MM)

MINIMUM

RISER

GAS

CONTROL

TUBING

GAS

SUPPLY

HORIZONTAL

DROP

3 IN.

(76 MM)

MINIMUM

RISER

M3077

2

1

2

2

1

2

ALL BENDS IN METALLIC TUBING SHOULD BE SMOOTH.

CAUTION:  SHUT OFF THE MAIN GAS SUPPLY BEFORE REMOVING

END CAP TO PREVENT GAS FROM FILLING THE WORK AREA.  TEST 

FOR GAS LEAKAGE WHEN INSTALLATION IS COMPLETE.

TWO IMPERFECT 

THREADS

GAS CONTROL

THREAD PIPE THE AMOUNT 

SHOWN IN TABLE FOR 

INSERTION INTO GAS CONTROL 

APPLY A MODERATE AMOUNT OF

PIPE COMPOUND TO PIPE ONLY

(LEAVE TWO END THREADS BARE).

M3075B

PIPE

Summary of Contents for 1000 Series

Page 1: ... 1000 Btu ft3 0 64 sp gr natural gas at 1 in wc pressure drop 37 3 MJ m3 0 64 sp gr natural gas at 0 25 kPa pressure drop b Minimum and Maximum regulation is at the max fire Minimum regulation at low fire is 9 KBtu h at 0 7 in WC outlet pressure SPECIFICATIONS Body Pattern Straight through see Table 1 for inlet and outlet size Electrical Ratings Voltage and Frequency 24 Vac 50 60 Hz Current Draw 0...

Page 2: ...d applications with greater cycling rates the control can wear out more quickly Perform a monthly checkout Water or Steam Cleaning If a control gets wet replace it If the appliance is likely to be cleaned with water or steam protect cover the control and wiring from water or steam flow Mount the control high enough above the bottom of the cabinet so it does not get wet during normal cleaning proce...

Page 3: ...nician Force or attempted repair may result in fire or explosion 5 Plan the installation as outlined below 6 Plan for frequent maintenance as described in the maintenance section Mounting position The valve can be mounted 0 to 90 degrees in any direction from the top of the valve facing up including outlet facing upward or downward See Fig 2 If the valve is mounted horizontally the top of the valv...

Page 4: ...pling to connect the tubing to the control 3 Install a sediment trap in the supply line to the control See Fig 3 Install Control 1 Mount with the coils 90 degrees from the vertical upright position 2 Mount so the gas flow is in the direction of the arrow on the bottom of the control 3 Thread the pipe the amount shown in Table 3 for insertion into control or adapters Do not thread pipe too far Valv...

Page 5: ...ed on valve operator On Off Switch The on off switch settings are as follows OFF Prevents main gas flow through the control ON Permits gas to flow into the control body Under control of the thermostat and direct ignition module gas can flow to the main burners CAUTION Equipment damage Can burn out valve coil terminals Never apply a jumper across or short the valve coil terminals even temporarily I...

Page 6: ...at Gas Leak Test at plug with main burner operating Pressure Tap The combination gas control is provided with 1 8 in NPT pressure tap plugs The gas air module is provided with 9 mm O D tubing connections to sense the high and the low combustion air pressure CAUTION To ensure a safe closing of the valves it is essential that power supplied to the gas valve be disconnected Minimum Regulator Offset a...

Page 7: ...If proper voltage is present replace gas control INSTRUCTIONS TO THE HOMEOWNER WARNING Fire or Explosion Hazard Can cause property damage severe injury or death Follow these warnings exactly 1 Before lighting smell around the appliance for gas Be sure to smell next to the floor because LP gas is heavier than air If you smell gas a Turn off the gas supply at the appliance service valve On LP gas sy...

Page 8: ...ell com U S Registered Trademark 2009 Honeywell International Inc 69 2305 03 M S Rev 02 09 Turning Off the Appliance Vacation Shutdown Set the thermostat to the desired room temperature while you are away Complete Shutdown 1 Turn off power to the appliance 2 Turn off the gas supply to the appliance 3 Push the on off switch to the OFF position Appli ance will completely shut off 4 Follow the proced...

Reviews: