ERV/HRV Ventilation Systems 69-2480EF—19
7
Specifications (continued)
External Static Pressure
Net Supply Air Flow
Gross Air Flow
Supply
Exhaust
Pa
in. W.C.
L/s
CFM
L/s
CFM
L/s
CFM
25
0.1
97
207
99
210
99
211
50
0.2
89
189
91
193
91
193
75
0.3
88
187
84
179
84
178
100
0.4
75
159
76
162
76
162
125
0.5
70
148
71
150
69
147
150
0.6
62
131
63
133
62
131
175
0.7
55
116
55
118
55
117
200
0.8
49
104
50
106
48
102
225
0.9
42
90
43
91
43
92
250
1.0
36
77
37
78
40
86
275
1.1
32
68
32
69
32
69
Supply Temperature
Net Supply Air Flow
Average
Power
Sensible
Recovery
Apparent
Sensible
°C
°F
L/s
CFM
Watts
Efficiency %
Effectiveness %
Heating
0
32
24
51
58
65
76
0
32
38
80
76
65
73
0
32
56
118
96
62
70
-15
5
26
55
59
52
78
35
95
30
64
66
VNT5150E1000 Ventilation Performance
VNT5150E1000 Energy Performance
Total Recovery Efficiency = 34%
VNT5150E1000
AIR FLOW (L/S)
AIR FLOW (CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W. C)
EXTERNAL
STATIC
PRESSURE
(PA)
M32370A
0.0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0
50
100
150
200
250
0
25
50
75
100
125
150
175
200
0
10
20
30
40
50
60
70
80
90
100
110
NET SUPPLY AIR FLOW