ERV/HRV Ventilation Systems 69-2480EF—19
12
Specifications (continued)
External Static
Pressure
Net Supply Air Flow
Gross Air Flow
Supply
Exhaust
Pa
in. W.C.
L/s
CFM
L/s
CFM
L/s
CFM
25
0.1
122
258
126
260
120
254
50
0.2
114
241
115
242
111
235
75
0.3
105
223
106
225
103
218
100
0.4
98
207
99
209
94
199
125
0.5
89
189
90
190
85
180
150
0.6
81
172
82
174
76
161
175
0.7
72
152
73
154
67
142
200
0.8
63
133
64
135
58
123
225
0.9
56
119
57
121
50
106
250
1.0
48
102
48
102
42
89
275
1.1
41
87
42
88
35
74
VNT6200H1000 Ventilation Performance
VNT6200H1000 Energy Performance
Supply Temperature
Net Supply Air Flow
Average
Power
Sensible
Recovery
Apparent
Sensible
°C
°F
L/s
CFM
Watts
Efficiency %
Effectiveness %
Heating
0
32
29
61
62
78
90
0
32
43
91
74
76
85
0
32
60
127
92
73
80
-25
-13
31
66
59
66
88
0.0
0.1
0.2
0.3
0.4
0.6
1.0
0.9
1.1
0
50
100
150
200
300
25
50
75
100
125
150
175
200
0
10
20
30
40
50
60
70
80
90
100
110
VNT6200H1000
AIR FLOW (L/S)
AIR FLOW (CFM)
EXTERNAL
STATIC
PRESSURE
(IN. W. C)
EXTERNAL
STATIC
PRESSURE
(PA)
M34366
250
0
0.5
NET SUPPLY AIR FLOW
0.7
0.8
1.2