background image

GB

4

MU0H-1155GE23 R0319

7

Start-up

7.1 Setting outlet pressure

Set outlet pressure min. 1 bar under inlet pressure. 

1.

Close shut-off valve on inlet

2.

Release pressure on outlet side (e.g. through water tap)

3.

Close shut-off valve on outlet

4.

Loosen slotted screw

Do not remove slotted screw

5.

Slacken tension in compression spring

Turn adjustment handle counter clockwise (-) until 
it does not move any more

6.

Slowly open shut-off valve on inlet

7.

Turn control handle until the setting scale shows the 
desired value

8.

Re-tighten slotted screw

9.

Slowly open shut-off valve on outlet

7.2 Reverse rinsing

CAUTION!

Interval: 

at least every 6 month (acc. to EN806-5)

every 2 months (manufacturer's recommendation) 
resp. depending on the degree of dirt in the water.

Red pointer integrated into the view window of one of 
the pressure gauges  for setting the next reverse 
rinsing
Date for next reverse rinsing can be set at the memory 
indicator of the outlet pressure gauge. 
To ensure convenient and regular adherence to the 
reverse rinsing interval, we recommend installing an 
automated reverse rinsing system Z11AS.

During reverse rinsing, an inlet pressure of at least 
1.5bar is required.
Filtered water can also be tapped during reverse 
rinsing.

To avoid extra abrasion, we recommend to perform the 
backwash at operating inlet pressures below 12 bar.

7.2.1 Manual reverse rinsing

A collecting container must be positioned beneath 
before reverse rinsing if there is not drainage system 
available.

1.

Slowly open the ball valve

The patented reverse rinsing system starts

2.

Close ball valve again after approx. 3-5 seconds. 
Repeat procedure three times

If the filter is extremely dirty, the procedure may 
have to be repeated additional times

7.2.2 Automatic reverse rinsing with the 

Z11AS

The automated reverse rinsing system Z11AS is available as 
an accessory. The automated system reliably takes over 
reverse rinsing of the filter at intervals which can be set 
between 4 minutes and 3 months.

7.2.3 Differential pressure controlled 

reverse rinsing with the DDS76 and 

Z11AS

Also available as an accessory is the DDS76 differential 
pressure switch. It provides fully automatic operation of the 
reverse rinsing which is controlled by the differential pressure 
across the filter. It actuates a reverse rinsing cycle when the 
pressure differential between the inlet and outlet of the filter 
reaches a predetermined value. If the pressure difference 
exceeds the preset value, then the Z11AS reverse rinsing 
actuator is operated via its volt-free input.

8

Maintenance

8.1 Inspection

We recommend taking out a servicing contract with an 
installation firm
In accordance with EN 806-5, the following measures 
must be taken:

8.1.1 Check valve

Interval: once a year

1.

Close shut-off valve on inlet

2.

Open test valve

Until the pressure is released, some water will flow 
out of the test valve. After a short period of time the 
water flow should stop. If the water continues to 
drip or run, then the check valve must be replaced 
- see servicing of check valve

3.

Close test valve again

4.

Slowly open shut-off valve on inlet

8.1.2 Filter

CAUTION!

Interval: 

at least every 6 month (acc. to EN806-5)

every 2 months (manufacturer's recommendation) 
resp. depending on the degree of dirt in the water.

An increased differential pressure between inlet and 
outlet pressure gauge indicates a highly contaminated 
filter.

Summary of Contents for HS10S FA Series

Page 1: ...R32344916 001 HS10S FA Installation instructions Einbauanleitung Keep instructions for later use Water station Anleitung zum sp teren Gebrauch aufbewahren Wasserstation...

Page 2: ...ater needed for cleaning the filter passes through the upper filter section then the rotating impeller with jets and the main filter from inside to outside i e the filter is reverse rinsed with filter...

Page 3: ...harge connection at the filter and the sewage piping e g drain connection with syphon has to be 56mm at least To do this there are 3 options 1 Discharge into floor drain 2 Drain into open container 3...

Page 4: ...ter approx 3 5 seconds Repeat procedure three times If the filter is extremely dirty the procedure may have to be repeated additional times 7 2 2Automatic reverse rinsing with the Z11AS The automated...

Page 5: ...l 8 Screw filter bowl in place 9 Slowly open shut off valve on inlet 10 Slowly open shut off valve on outlet 8 2 4Replace filter mesh 1 Close shut off valve on inlet 2 Release pressure on outlet side...

Page 6: ...s escaping from the spring bonnet Diaphragm is faulty Replace diaphragm Spring bonnet not screwed flush Retighten the screws O ring forgotten in the diaphragm piston during assembly Insert O ring Too...

Page 7: ...65C Filter mesh 50 m DN80 AF78TS 080C Filter mesh 50 m DN100 AF78TS 100C 2 Replacement sieve Filter mesh 100 m DN65 ES78TS 065A Filter mesh 100 m DN80 ES78TS 080A Filter mesh 100 m DN100 ES78TS 100A F...

Page 8: ...eren Filter ge ffnet Das f r die Filterreinigung ben tigte Wasser durchstr mt den oberen Filterbereich den rotierenden Impeller und anschlie end den unteren Filterbereich von innen nach au en d h die...

Page 9: ...ablaufs am Filter und der Abwasserableitung z B Trichter mit Syphon mindestens 56mm betragen Dazu gibt es 3 M glichkeiten 1 Ablauf frei in vorhandenen Bodenablauf 2 Ablauf in offenen Beh lter 3 Ablauf...

Page 10: ...sp len gegebenenfalls ein Auffanggef untergestellen 1 Kugelhahn langsam ffnen Das patentierte R cksp lsystem startet 2 Kugelhahn nach ca 3 5 Sekunden wieder schlie en Vorgang drei Mal wiederholen Wenn...

Page 11: ...ausgangsseitig langsam ffnen 8 2 2Filter 8 2 3Filtereinsatz ersetzen 1 Absperrarmatur eingangsseitig schlie en 2 Druck ausgangsseitig ablassen z B durch Wasserhahn 3 Absperrarmatur ausgangsseitig sch...

Page 12: ...rgung siehe Kapitel 4 Lieferumfang Die rtlichen Vorschriften zur korrekten Abfallverwertung entsorgung beachten 10 Fehlersuche Problem Ursache Abhilfe Schlagende Ger usche Druckminderer zu gro dimensi...

Page 13: ...lterfeinheit 50 m DN80 AF78TS 080C Filterfeinheit 50 m DN100 AF78TS 100C 2 Ersatzsieb untere obere Durchlass weite 105 135 m DN65 ES78TS 065A untere obere Durchlass weite 105 135 m DN80 ES78TS 080A un...

Page 14: ...261 810 Fax 49 6261 81309 Manufactured for and on behalf of the Pittway S rl La Pi ce 4 1180 Rolle Switzerland by its Authorised Representative Ademco 1 GmbH MU0H 1155GE23 R0319 Subject to change 2019...

Page 15: ...Assembly 3 7 Start up 4 8 Maintenance 4 9 Disposal 6 10 Troubleshooting 6 11 Spare Parts 7 12 Accessories 7 D 1 Sicherheitshinweise 8 2 Funktionsbeschreibung 8 3 Technische Daten 8 4 Lieferumfang 8 5...

Page 16: ...16 MU0H 1155GE23 R0319 7 min 200mm 4 8 7 6 5 120l 2 1 3 min 250mm min 56mm min 56mm min DN70 4 11 10 5 8 6 7 1 5 2Nm 9 12Nm 9 12Nm 4 5 6 7 1 2 2 3 6 7 2 1 8 2 3 8 2 4 6 3 7 1 8 1 1 4...

Page 17: ...MU0H 1155GE23 R0319 17 4 5 7 6 4 5 6 8 2 6 11 11 8 3 1 11 6 5 8 7 7 8 8 8 8 8 8 8 9 8 8 8 5 8 6 8 8 7 9 8 7 8 11 10 10 11 11 11 11 12 11 11 13 1 2 4 4 3 1 2 4 3 3 4...

Reviews: