MOUNTING

The following procedure describes a typical side installation on an existing highboy furnace (Fig. 1). Alternate 
procedures are noted as appropriate. Other changes in installation procedures may be necessary to complete 
your installation.

NOTE:

  Before starting the installation, remove and discard the existing furnace filter (if used). Thoroughly 

clean the blower compartment. If possible, power vacuum the ductwork to remove accumulated dust 
in an occupied home or remove construction dirt in a new home. The media air cleaner cannot remove 
dirt that has settled in the blower compartment and distribution ducts.

STEP ONE: Review the Installation Plan

Temporarily place the cabinet on the floor, oriented as it will be when installed. Insert and remove the 
cartridge to make sure the plan allows adequate clearance for easy removal and replacement of the cartridge.

STEP TWO: Fasten the Cabinet to the Furnace

a.  Align the cabinet with the return air opening. 
b.  Place blocks under the cabinet, as necessary, to make sure the unit sits securely. 
c.  Create an opening in the furnace to match the cabinet opening. 
d.  Attach the cabinet securely to the furnace. Attach the unit directly or fit a starting collar in the furnace 

opening. Either drill holes and fasten with sheetmetal screws or rivets, or use slip joints. If you are drilling 
holes, use a locking pliers to help hold the unit in place during drilling.

STEP THREE: Install Turning Vanes

Install turning vanes to help distribute air equally over the full surface of the upstream side of the media. 
Install them whenever an abrupt 90 degree elbow is installed directly against the media air cleaner cabinet.

STEP FOUR: Fasten Cabinet to Ductwork

Fasten side of cabinet to the ductwork using sheet-metal screws, rivets, or slip joints, as appropriate.

STEP FIVE: Connect Ductwork

a.  Connect the vertical duct section to the elbow. If the vertical drop of the duct is less than 7 in. (178 mm) 

from the side of the furnace, shorten the horizontal trunk or attach an offset fitting to the elbow. 

b.  When ductwork is properly aligned, connect the vertical duct to the horizontal trunk.

STEP SIX: Seal Joints

Seal all joints in the return air system between the media air filter and the furnace to prevent dust from 
entering the clean airstream.

STEP SEVEN: Install Filter Cartridge

Slide the filter cartridge into the cabinet, making sure the arrow on the cartridge points in the direction of air 
flow. Replace access door. Insert the tab on the bottom of the door into the slot in the cabinet. Swing the door 
closed and press it into place.

Mounting the Media Air Cleaner

Media Air Cleaner   68-0239EF—13

7

Summary of Contents for F100F

Page 1: ... x 12 5 FC100A1052 N A 20 x 20 FC100A1011 FC200E1011 20 x 25 FC100A1037 FC200E1037 21 5 x 27 5 FC100A1045 N A 25 x 20 FC100A1037 FC200E1037 25 x 22 FC100A1037 FC200E1037 Media Air Cleaner Size in F100 Media Air Cleaner w MERV 11 Filter F200 Media Air Cleaner w MERV 13 Filter 16 X 25 F100F1625 F200F1625 16 X 20 F100F1620 F200F1620 20 X 25 F100F2025 F200F2025 20 X 20 F100F2020 F200F2020 25 X 22 F100...

Page 2: ... allowed to continue through your heating and cooling system and into your home The particle removal efficiency of the Media Air Cleaner can be found in the Specification section of this manual What to Expect From Your Media Air Cleaner Application Considerations The Media Air Cleaner is designed to work with gas oil and electric forced warm air furnaces and with compressor cooling It can also be ...

Page 3: ... See middle figure Sheetmetal The media air cleaner is adaptable to all new or existing forced air heating and cooling systems used in residential applications Transitions or turning vanes may be required in some applications for effective media air cleaner operation Offsets If the duct connection to the furnace in a side installation allows less than 7 in 178 mm for mounting media air cleaner cab...

Page 4: ...in front of the unit for removal of the cartridge Install the media air filter where the temperature will not exceed the ratings in the Specifications Do not mount in the supply air duct NOTE Generally the best location is in the return air duct next to the blower compartment so the media air cleaner can help to keep the blower motor and evaporator coils clean If Replacing an Old Air Cleaner If th...

Page 5: ... coil M939C M940C Choosing a Mounting Position Before beginning Mounting I have chosen an installation location that meets the requirements on pages 5 through 6 Fig 1 Highboy furnace with side installation Media air filter is mounted vertically where return enters side inlet of furnace Fig 2 Highboy furnace with installation beneath furnace Media air cleaner is mounted horizontally where return en...

Page 6: ... media air cleaner mounted horizontally in return duct or plenum just above furnace Fig 6 Central fan installation with media air cleaner mounted horizontally in central return duct M945C M946C Fig 7 Horizontal furnace with media air filter mounted vertically in return duct near furnace Fig 8 Two or more media air cleaners used in a high capacity system Media Air Cleaner 68 0239EF 13 6 ...

Page 7: ...e opening Either drill holes and fasten with sheetmetal screws or rivets or use slip joints If you are drilling holes use a locking pliers to help hold the unit in place during drilling STEP THREE Install Turning Vanes Install turning vanes to help distribute air equally over the full surface of the upstream side of the media Install them whenever an abrupt 90 degree elbow is installed directly ag...

Page 8: ...e drop across the media filter reaches 0 5 in w c 0 1 kPa or at least annually If the media air cleaner is installed downstream from an atomizing humidifier or if the installation includes both heating and cooling more frequent replacement may be necessary Clogged media must be replaced promptly to avoid restricting airflow and reducing efficiency of the heating cooling system Record the replaceme...

Page 9: ...0 in 508 x 508 mm 16 x 25 in 406 x 635 mm 16 x 20 in 406 x 508 mm M37054A F100F SIZE IN 16 X 25 16 X 20 20 X 25 20 X 20 25 X 20 25 X 22 MM 406 X 635 406 X 508 508 X 635 508 X 508 635 X 508 635 X 559 DIM A 14 1 4 14 1 4 18 1 4 18 1 4 23 1 8 23 1 8 362 362 464 464 587 587 DIM B 16 1 4 16 1 4 20 3 16 20 3 16 25 3 16 25 3 16 413 413 513 513 640 640 23 1 4 18 1 4 23 1 4 18 1 4 18 1 4 20 1 4 DIM C 591 4...

Page 10: ...m This product is manufactured by Resideo Technologies Inc Golden Valley MN 1 800 468 1502 2019 Resideo Technologies Inc The Honeywell Home trademark is used under license from Honeywell International Inc All rights reserved 68 0239EF 13 M S Rev 11 19 Printed in United States ...

Page 11: ... FC200E1037 25 x 22 FC100A1037 FC200E1037 Dimension de l épurateur d air po Épurateur d air F100 avec filtre MERV 11 Épurateur d air F200 avec filtre MERV 13 16 X 25 F100F1625 F200F1625 16 X 20 F100F1620 F200F1620 20 X 25 F100F2025 F200F2025 20 X 20 F100F2020 F200F2020 25 X 22 F100F2051 N A 25 X 20 F100F2044 N A Épurateurs d air à fibres PROFESSIONAL INSTALLATION GUIDE GUIDE D INSTALLATION PROFESS...

Page 12: ...ns le système de chauffage et de refroidissement et aère la maison L efficacité du nettoyage des particules de l Épurateur d air à fibres est spécifiée dans la section Caractéristiques techniques de ce manuel À propos de l épurateur d air à fibres Considérations relatives à l application L Épurateur d air à fibres est conçu pour fonctionner avec les appareils de chauffage à gaz mazout électrique e...

Page 13: ...res peut être adapté à tous les systèmes de chauffage et de refroidissement à air pulsé neufs ou existants utilisés dans les applications résidentielles Des transitions ou des aubes directrices peuvent être requises dans certaines applications pour une épuration de l air plus efficace Déviations Si la connexion de la gaine à l appareil de chauffage dans une installation latérale alloue un espace i...

Page 14: ...filtre Installer le filtre à air à fibres à un endroit où la température ne dépasse pas les valeurs indiquées dans la section Caractéristiques techniques Ne pas monter l appareil dans la gaine d air d alimentation REMARQUE De manière générale le meilleur emplacement est dans la gaine d air de retour près du compartiment de la soufflante pour favoriser la propreté du moteur de la soufflante et des ...

Page 15: ...mmencer le montage J ai choisi un emplacement d installation qui répond aux exigences des pages 5 à 6 M939C M940C Fig 1 Appareil de chauffage superposé avec installation latérale Le filtre à air à fibres se monte verticalement à l endroit où l air de retour pénètre dans l entrée latérale de l appareil de chauffage Fig 2 Appareil de chauffage superposé avec installation sous l appareil de chauffage...

Page 16: ...horizontalement dans la gaine de retour ou le plénum juste au dessus de l appareil de chauffage Fig 6 Installation de ventilation centrale avec épurateur d air à fibres monté horizontalement dans la gaine de retour centrale M945C M946C Fig 7 Appareil de chauffage horizontal avec filtre à air à fibres monté verticalement dans la gaine de retour près de l appareil de chauffage Fig 8 Deux épurateurs ...

Page 17: ...rt dans l ouverture de l appareil de chauffage Percer des trous et fixer avec des vis à tôle ou des rivets ou utiliser des joints coulissants Si des trous sont percés utiliser des pinces de verrouillage pour maintenir l ouverture en place durant le perçage ÉTAPE 3 Installation des aubes directrices Installer les aubes directrices pour favoriser une distribution égale de l air sur toute la surface ...

Page 18: ...la chute de pression sur le filtre à fibres atteint 0 1 kPa 0 5 po c e ou une fois par an au minimum Si l épurateur d air à fibres est installé en aval d un humidificateur à pulvérisation ou si l installation inclut chauffage et refroidissement un remplacement plus fréquent peut être requis Un filtre obstrué doit être rapidement remplacé pour éviter les restrictions du débit d air et une réduction...

Page 19: ... LA CHUTE DE PRESSION ATTEINT 0 5 PO C E 0 1 kPa DISPONIBLE AUX ÉTATS UNIS SEULEMENT 2 1 1 2 Caractéristiques du F200 Valeur MERV MERV 13 Chute de pression statique 0 3 PO C E 2 54 m s Cotes d efficacité Petites particules E1 0 3 à 1 0 microns 63 Particules moyennes E2 1 0 à 3 0 microns 91 Grosses particules E3 3 0 à 10 0 microns 99 0 500 1000 1500 2000 0 0 1 0 2 0 3 0 4 CHUTE DE PRESSION PO C E D...

Page 20: ... est fabriqué par Resideo Technologies Inc Golden Valley MN 1 800 468 1502 2019 Resideo Technologies Inc La marque de commerce Honeywell Home est utilisée sous licence avec l autorisation d Honeywell International Inc Tous droits réservés 68 0239EF 13 M S Rev 11 19 Imprimé aux États Unis ...

Reviews: