EV6010
6-449
c. The generator starts and runs, but won’t stop when the stop button is pushed.
Before installing a new control box it is important to check two possible causes of the problem.
1. The remote is not wired correctly. The brown and white (Honda colors) wires are reversed. See page
13-1 of the base shop manual for correct wiring.
2. The wire in the remote harness has been grounded by damage to the insulation.
NOTICE
Attaching the battery positive (+) to the wire coming from the control box to the fuel pump will instantly
destroy the control box. The fuel pump positive lead should be disconnected from the control box and the
male end of the wire (leading to the pump) attached to the battery.