HOLOPHANE Predator LED Flood Medium Installation And Maintenance Manual Download Page 4

 

 

 

IM-365-A 

 

2.2.3 

For units with a photocontrol receptacle, the mounting must be 

restricted to ± 45° from horizontal aim per ANSI C136.10-2010. 

2.2.4 

Tighten the 1/2" diameter yoke bolts securely (approx. 50 ft.lb. 

recommended).  See Figure 1. 

2.2.5 

Energize the floodlight. Check its operation and check for 

proper area illumination. Adjust the aiming point as needed within the 
limits of the mounting restrictions. 

 

Figure 3 

 

 

GR2277 

 

2.3  Knuckle Fitter Mount Installation.

 

This luminaire is pre-wired with UL listed supply wire leads, so it is not 
necessary to open the housing door to install or wire the luminaire. If 
access to the interior of the housing is necessary, refer to the 
MAINTENANCE section (SECTION 3) below. 

2.3.1 

Slip the slip fitter of the knuckle fitter over the pole-top, tenon or 

pipe bracket. Lightly tighten all four set screws evenly against the pole-
top, tenon or pipe bracket. 
 

WARNING 

DO NOT MOUNT THE KNUCKLE FITTER TO A TENON OR 
BRACKET THAT IS MORE THAN 30 DEGREES FROM 
VERTICAL.  MOUNTING AT AN ANGLE GREATER THAN 30 
DEGREES MAY RESULT IN DISENGAGEMENT OF THE 
FITTER AND RESULT IN SERIOUS INJURY OR DEATH. 
 

2.3.2 

Removed wiring cover from knuckle fitter. 

2.3.3 

Make all wiring connections inside the wiring chamber in 

accordance with approved wiring methods. 

2.3.4 

Replace the knuckle fitter wiring cover. 

2.3.5 

For units with a photocontrol receptacle, the mounting must be 

restricted to ± 45° from horizontal aim per ANSI C136.10-2010. 

2.3.6 

Tighten the 3/8" diameter knuckle fitter bolt securely (approx. 

16 ft.lb. recommended). Tighten (4) 3/8 set screws to 16 ft.lb. See 
Figure 3. 

2.3.7 

Energize the floodlight. Check its operation and check for 

proper area illumination. Adjust the aiming point as needed within the 
limits of the mounting restrictions. 
 
 
 
 
 
 
Figure 4 

 

 

GR2282 

 

2.4  DM Option 

For units equipped with 0-10V dimming, locate the gray and violet 
leads in the knuckle wiring chamber or inside the unit for the yoke 
mount options. These are to be used with a Holophane approved 
control circuit. Connect supply dimming leads to dimming leads in the 
wiring chamber next to the terminal block. VIOLET IS POSITIVE, 
GRAY IS NEGATIVE. 
 

CAUTION 

IT IS NECESSARY THAT THE POLARITY OF THE DIMMING 
CONTROL LEADS TO THE FIXTURE BE MAINTAINED. 
CROSSING OF THE POLARITY WILL CAUSE IMPROPER 
AND UNEXPECTED DIMMING RESULTS AND MAY LEAD 
TO DAMAGE TO THE DRIVER DIMMING CIRCUITS. 

 
 

MAINTENANCE 

 

3.1  Cleaning of Luminaire

 

3.1.1 

Wipe off exterior dirt and debris using a soft clean cloth.  A mild 

detergent and water may be used if necessary. 
 

CAUTION 

DO NOT USE ABRASIVE CLEANERS ON OPTICAL 
SURFACES.  THEIR USE MAY RESULT IN THE LOSS OF 
OPTICAL EFFICIENCY. 

  

3.2  Electrical Component Replacement 

Reviews: