2.4 Electrical Connection of Optical housing to 
Electrical Housing (Figure 5, 7) 
2.4.1 

Determine length of conduit/supply wires needed 

to connect the Electrical Housing to the Optical Housing. 
Be sure to maintain a minimum length of 5 feet to ensure 
required minimum mounting distance between optical 
and electrical housings. Maximum lengths are based on 
wire gage and can be found on Table 2. 

2.4.2

 The supply wires should extend 6 inches beyond 

the flex conduit for wiring inside the Electrical Housing 
junction box and outlet box. 

2.4.3

 Open the junction box mounted to the top of the 

Electrical Housing by loosening the wingnut securing the 
two halves of the box together such that the lid can 
rotate on its hinge. 

2.4.4

 Feed connection wires into Electrical Housing 

junction box via the knockout holes in the lid 

2.4.5

 Connect each set of stem conductor leads to a set 

of input leads. Be sure to label each set of input leads in 
case of future maintenance. Make all wiring connections 
in accordance with all local electrical codes. 

2.4.6

 Attach flex conduit to Electrical Housing junction 

box vi

a the ¾” NPT knockouts 

2.4.7

 Feed wires at the other end of the flex conduit into 

customer provided outlet box that the Optical Housing is 
mounted to and make all wiring connections in 
accordance with all local electrical codes. 

2.4.8

 Do not pull supply leads beyond 6 inches or 

electrical housing wire connections could be pinched or 
damaged. 

 
 

TABLE 2  

Maximum Supply Lead Length for Remote PHZL 

 

WIRE GAGE 

MAX. LENGTH (FEET) 

18 AWG 

70 

16 AWG 

120 

14 AWG & larger 

150 

 

CAUTION 

MOUNT ELECTRICAL HOUSING 4 FEET AWAY 
HORIZONTALLY FROM THE OPTICAL HOUSING TO 
ENSURE ELECTRICAL COMPONENTS DO NOT 
EXCEED THEIR MAX TEMPERATURE LIMITS.   

 

2.5 Electrical Housing Supply Wiring (Figure 5, 7)

 

2.5.1 

Supply wiring connections to the Electrical Housing 

are to be made inside the junction box mounted on top 
(Figure 5). Supply connection leads should be present 
inside the junction box. If supply connection leads are 
not present inside the Electrical Housing junction box, 
refer to section 3.1 on how to access the Electrical 
Housing. 

2.5.1.1 

After accessing the Electrical Housing, 

retrieve supply connection leads and feed them 
back through the top of the Electrical Housing 
back into the junction box. 

2.5.1.2 

Close the Electrical Housing. Ensure all 

leads are completely inside enclosure and not 
pinched. 

2.5.2 

For supply wiring, make all wiring connections in 

accordance with all local electrical codes. 

2.5.3

 Shut junction box lid and tighten wingnut onto the 

supplied J-bolt, ensuring all leads are completely inside 
enclosure and not pinched. 

 

Figure 5 

 

GR2440 

 

 

2.6 Optional 0-10V DC Dimming Wiring (Figure 5)

 

2.6.1 

Optional low voltage dimming terminal is located 

on top of the Electrical Housing. 

2.6.2 

Connect supply dimming leads to the Gray (-) and 

Violet (+) DC dimming leads located on the dimming 
terminal.   

 
2.7 Flex Conduit to Stem Wiring 
2.7.1 

For Flex Conduit wiring, remove (1) KO from 

junction box (not provided) and insert flex conduit fitting 
into KO and secure in place. 

2.7.2 

Connect green lead to ground lead. 

2.7.3

 Connect each set of stem conductor leads to a set 

of input leads. Be sure to label each set of input leads in 
case of future maintenance.  

2.7.4

 Close junction box and secure Swivel Dome per 

section 2.3

 

 

Summary of Contents for Phuzion PHZL

Page 1: ...ic products please visit www epa gov These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation...

Page 2: ...ndividual product specifications deem otherwise Never connect an LED product directly to a dimmer packs occupancy sensors timing devices or other related control devices LED fixtures must be powered d...

Page 3: ...or Stem Set Screw 3 8 socket Electrical housing surface mount 2 2 Stem to Optical Housing Installation Figure 2 3 2 2 1 Ensure the ground wire and all 3 sets of input leads are present and accessible...

Page 4: ...al Housing by placing the stem fitting onto the hook bracket and install cotter pin 2 3 6 Route leads from mounting stem into the outlet box 2 3 7 Slide cover and swivel dome up stem Secure swivel dom...

Page 5: ...GAGE MAX LENGTH FEET 18 AWG 70 16 AWG 120 14 AWG larger 150 CAUTION MOUNT ELECTRICAL HOUSING 4 FEET AWAY HORIZONTALLY FROM THE OPTICAL HOUSING TO ENSURE ELECTRICAL COMPONENTS DO NOT EXCEED THEIR MAX...

Page 6: ...2 6 3 Mount Electrical Housing using fasteners properly sized to support the weight of the Electrical Housing fasteners not provided Figure 6 GR2435 2 10 Safety Chain Option 2 10 1 Safety chain optio...

Page 7: ...ready labeled 3 1 4 Replace components using Holophane approved replacement parts 3 1 5 Re connect electrical leads 3 1 6 Shut electrical door and tighten door screws ensuring all leads are completely...

Reviews: