HOLOPHANE Phuzion PHZL Installation And Maintenance Manual Download Page 3

HOLOPHANE

®

 

Phuzion

TM 

 PHZL Remote 

Installation and 

 

Highbay Luminaire 

Maintenance 

                     

                                                     Manual 

 

 

IM-394 

 

Figure 1 

 

GR2438 

 
1 Introduction 
1.1 Product Description.

  The Phuzion

TM 

PHZL Remote 

LED fixtures have been designed and tested in 
accordance with applicable UL/CSA standards and are 
suitable for use in damp locations.  The remote fixture 
will come with an Electrical Housing set up for hook 
and/or surface mounting. The Optical Housing will be 
separate and require a rigid stem attachment. Optical 
Housing max weight is 30 lbs. Electrical Housing max 
weight is 25 lbs. 
 

2 Installation 
2.1  Tools and Materials Required. 
 

TABLE 1 

Installation Tools and Materials 

 

DESCRIPTION 

 

USE 

 

 

 

5/16” socket 

Electrical Door, Stem Set Screw 

3/8” socket 

Electrical housing surface  

 

 

mount 

 

2.2 Stem to Optical Housing Installation (Figure 2, 3) 
2.2.1 

Ensure the ground wire and all (3) sets of input 

leads are present and accessible from both ends of the 
stem. Do not remove labels from set of red & blue leads. 

2.2.2 

Remove cover from the wiring chamber of the 

Optical Housing (Figure 2). Ensure that the Optical 
Housing contains (3) sets of red & blue input wires and a 
ground wire.  

 
 

2.2.3 

Route all wires from the stem into Optical Housing 

wiring chamber via the 

¾” NPT hole and thread the rigid 

conduit into place, minimum 6 turns until tight.  

2.2.4 

Make all wiring connections inside the Optical 

housing wiring chamber in accordance with approved 
wiring methods. 

2.2.5

 Reinstall the wiring chamber cover and tighten the 

screws 

2.2.6

 Take care not to pinch any wires while closing the 

wiring chamber. 

 

Figure 2 

 

GR2442 

 

Figure 3 

 

GR2439 

 

 
 
 

Summary of Contents for Phuzion PHZL

Page 1: ...ic products please visit www epa gov These instructions do not purport to cover all details or variations in equipment nor to provide every possible contingency to meet in connection with installation...

Page 2: ...ndividual product specifications deem otherwise Never connect an LED product directly to a dimmer packs occupancy sensors timing devices or other related control devices LED fixtures must be powered d...

Page 3: ...or Stem Set Screw 3 8 socket Electrical housing surface mount 2 2 Stem to Optical Housing Installation Figure 2 3 2 2 1 Ensure the ground wire and all 3 sets of input leads are present and accessible...

Page 4: ...al Housing by placing the stem fitting onto the hook bracket and install cotter pin 2 3 6 Route leads from mounting stem into the outlet box 2 3 7 Slide cover and swivel dome up stem Secure swivel dom...

Page 5: ...GAGE MAX LENGTH FEET 18 AWG 70 16 AWG 120 14 AWG larger 150 CAUTION MOUNT ELECTRICAL HOUSING 4 FEET AWAY HORIZONTALLY FROM THE OPTICAL HOUSING TO ENSURE ELECTRICAL COMPONENTS DO NOT EXCEED THEIR MAX...

Page 6: ...2 6 3 Mount Electrical Housing using fasteners properly sized to support the weight of the Electrical Housing fasteners not provided Figure 6 GR2435 2 10 Safety Chain Option 2 10 1 Safety chain optio...

Page 7: ...ready labeled 3 1 4 Replace components using Holophane approved replacement parts 3 1 5 Re connect electrical leads 3 1 6 Shut electrical door and tighten door screws ensuring all leads are completely...

Reviews: