41
10.3 Key parts checking.
10.3.1. Compressor checking
Measure the resistance value of each winding by using the multi-meter.
10.3.2 Outdoor Fan Motor
Measure the resistance value of each winding by using the multi-meter.
10.3.3 Indoor Fan Motor
Measure the resistance value of each winding by using the multi-meter.
Position
Resistance Value
Blue - Red
HCNI 263-353
1.10Ω
(20
℃
)
HCNI 503
0.668
Ω
(25
℃
)
Blue - Black
Red - Blue
Position
Resistance Value
Black - Red
350Ω
±8% (20
℃
) for 263
435Ω±8% (20
℃
) for 353
87.8Ω±8% (20
℃
) for 503
Blue - Red
222Ω
±8% (20
℃
) for 263
213Ω±8% (20
℃
) for 353
Red -Yellow
141.5
Ω
±8% (20
℃
) for 503
Yellow - Blue
222Ω
±8% (20
℃
) for 263
213Ω±8% (20
℃
) for 353
Position
Resistance Value
Black - Red
387
Ω±8% (20
℃
) for 263-353
Black - Red
270
Ω±8% (20
℃
) for 503
White - Black
378Ω±8% (20
℃
) for 263-353
White - Black
475
Ω±8% (20
℃
) for 503