10.2.9 P2 (temperature protection of compressor top) diagnosis and solution.
10.2.10 P4 (inverter compressor drive error) diagnosis and solution.
Is the connection of
compressor good? Is the
wiring sequence right?
The voltage range
proper?
Replace the outdoor E-box.
If the problem comes to
again, check coil
resistance of inverter
compressor, is it
1.10ohm?
YES
Replace inverter
compressor
Reconnect and retry
NO
NO
YES
Does
compressor
operate?
Is the
connection
good?
Is refrigerant
circulation
volume
normal?
NO
NO
Charge
refrigerant
Is abnormality
the same after
gas charging?
NO
Check refrigerant system
(such as clogging of
capillary, etc)
Reconnect and
retest.
NO
YES
Is protector
normal?
Replace the protector.
NO
YES
Check the
outdoor main
PCB. Is there
some problem?
Replace the outdoor PCB.
YES