10.2.6 E6 (open or short circuit of indoor room or evaporator temperature sensor) diagnosis and solution.
10.2.7 P0 (IGBT over-strong current protection) diagnosis and solution.
10.2.8 P1 (over voltage or too low voltage protection) diagnosis and solution.
Is all connections on PCB
and between PCB and
compressor good?
Repair or correct the
connector or connection.
Replace the outdoor
PCB and then repower
on. Is the failure
cleared?
NO
YES
Check the compressor
NO
Is the indoor
temperature and
evaporator sensor
connector and
connection good?
Repair the connector and
reconnect
Replace the sensor and
check if E6 display
again?
NO
YES
Replace the.indoor PCB
YES
Is the power supply
good?
Be sure the power supply
is normal when using the
units
NO
YES
Replace the outdoor
e-box.