OUT-92
DUAL, TRIPLE, POKER DC Inverter : 3. Outdoor Unitis & Troubleshooting
Multi Liberty
DC Inverter
•
Important warning for Safety:
On Outdoor Unit there are electrolytic condensers, that is high voltage components if system is powered,
even if it is not operating.
In case you need to have access to Outdoor Unit to carry out maintenance operations or repairing interven-
tions, in order to avoid the danger of electric shocks, it is recommended to wait at least 5 minutes after
disconnecting the system from power supply.
For example, on contacts P3, P4 of Outdoor Unit PCB there is high voltage: about 310V.
• Advice:
To discharge all remaining voltage in electrolytic condensers, the ends of a ceramic resistance of 1500
Ω
to
2000
Ω
may be put in contact with the terminals of each condenser.
This procedure is shown in the Figure above.
Electrolytic condenser
DANGER! HIGH VOLTAGE!
Ceramic resistance
Resistance values of temperature sensors (thermistors)
Temperature sensors on system are the following:
• T1 = Indoor temperature sensor.
• T2 = Temperature sensor on Indoor Unit’s heat exchanger.
• T3 = Outdoor air temperature sensor.
• T4 = Temperature sensor on Outdoor Unit’s heat exchanger.
• T5 = Temperature sensor on compressor discharge pipe.
• T
A
, T
B
, T
C,
T
D
= Pipe sensors Gas side, one for every Indoor Unit.
Concerning thermistors’ Resistance value based on temperature, please refer to the tables futher on, in this
Section “Outdoor Units & Troubleshooting” of this Service Manual.
3.3 ELECTRICAL SPECIFICATIONS OF SOME COMPONENTS