OUT-91
DUAL, TRIPLE, POKER DC Inverter : 3. Outdoor Unitis & Troubleshooting
Multi Liberty
DC Inverter
The display shows “P6”.
Overtemperature of outdoor heat exchanger.
Is temperature on outdoor heat exchanger > 65°C?
NO
NO
NO
NO
NO
YES
If temperature detected on oudoor heat exchanger is higher than 65°C, system is stopped.
Normal operation can be restored only when temperature value detected on outdoor heat exchanger is
lower than 52°C.
Check if R-T values of T3 sensor correspond to the
specifications indicated in the corresponding tables (see
further on).
Replace thermistor T3.
YES
YES
YES
YES
Replace Outdoor Unit’s
Control PCB.
Replace Outdoor Unit’s Control PCB.
Hypothesis 1:
Is outdoor temperature too high?
Hypothesis 2:
Is outdoor heat exchanger dirty or clogged?
Unit stops.
Clean outdoor heat exchanger.
Empty refrigerant (by recovering it). Eliminate
obstruction along the circuit, carry out the vacuum
procedure and the weighed out recharge of R410A.
Hypothesis 3:
- Is refrigerant circuit obstructed? Please check.
- Faulty EXV valve? Inspect.
- Excessive refrigerant amount? Measure pressure
values.
Overtemperature of Outdoor Unit’s heat exchanger
(in Cooling mode)
P 6
Outline of protection function
• Troubleshooting flowcharts, referred to Protection Codes displayed on Outdoor Unit:
Protection on Outdoor Unit