Terminal made by the construction team should be in a form of a permanent distributive damp-resistant socket (IP 65, at
least 30 cm over the
fl
oor, in the area under the bathtub).When installing a bathtub attention should be paid to the parts
containing active elements (except for items supplied with low safe voltage, i.e. not exceeding 12 V) which must not be
available for persons located in bathtub.
The fact that bathtub is connected to the electricity must be noted in the warranty card with signature and seal of the
authorised person, which determines validity of the guarantee.
02.04.1 Protected Area
⚠
Do not use unit without positive earth connection (PE,
)!
Interrupt current connection before opening!
area 1
area 1
area 2
area 2
60 cm
60 cm
area 2
60 cm
225 cm
r = 60 cm
area 0
area 0
L 1
L 2
L 3
N
PE
Main switch in bathroom
(Position outside area 2)
16A rccb
RCD 30 mA
Equipotential bonding 4 mm²