5. Set the
Input Latch
to Latching or Non-latching. For UL compliance, when
Input Action
is set to Fire or Carbon
Monoxide, this field must be set to Latching.
6. Each input circuit is Normally Open, but Closed upon activation. Selecting
Input Invert
will set the circuit to be
Normally Closed, but Open upon activation.
7. Set the
Location Text
, up to 80 characters. This text is displayed when the circuit is activated.
8. Set the desired
Map to Zone
number for the circuit. Allowable values are 0-2000.
UL Compliance Limitations
In order for the product to comply with the requirements in the
Standard for Control Units and Accessories
for Fire Alarm Systems, UL 864 10th Edition
, certain programming features or options must be limited to
specific values or not used at all as indicated below.
Field
Configurable Range
UL Permitted Value / Range
First Delay
0-10 minutes
0 minutes
Second Delay
0-10 minutes
0 minutes
Duration
0 seconds - 23 hours, 59 minutes, 50 seconds
0 seconds
Input Delay
0-180 seconds
0 seconds
Input Latch
Latching or Non-Latching
Latching, when Input Action is set to
Fire or Carbon Monoxide
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 | March 2021 | MAN-1420HA
Page 21
Configuration