First Delay
and
Second Delay
fields.
Second Delay
is only visible if the output is silenceable. For UL compliance,
both delays must be set to 0.
NOTE
If checked,
- the initial activation of the output will be delayed based on the settings in the First Delay field.
- if the output is silenceable, subsequent re-sounding of the output will be delayed based on the settings in the Second
Delay field.
5. Enter a
Duration
to select how long an output will be active. If set to 0, it will remain active until the system is reset.
For UL compliance, this field must be set to 0.
6. Set the
Location Text
, up to 80 characters.
7. Use the
Map to Zone
field to set the zone number for the circuit. Allowable values are 0-2000.
Hochiki America Corporation
16 Channel IO Panel Module (S772) Information Guide
Version 1.00 | March 2021 | MAN-1420HA
Page 19
Configuration