OM-926 Page 13
3-7.
Electrical Service Guide
50/60 Hz Models
Single Phase
Input Voltage
208
230
Input Amperes At Rated Output
33
30
Max Recommended Standard Fuse Or Circuit Breaker Rating In Amperes
Circuit Breaker
1
, Time-Delay
2
40
35
Normal Operating
3
50
45
Min Input Conductor Size In AWG/Kcmil
10
10
Max Recommended Input Conductor Length In Feet (Meters)
80
(24)
98
(30)
Min Grounding Conductor Size In AWG/Kcmil
10
10
Reference: 1999 National Electrical Code (NEC)
1 Choose a circuit breaker with time-current curves comparable to a Time Delay Fuse.
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).
Y
Caution: Failure to follow these fuse and circuit breaker recommendations could create an electric shock or fire hazard.
3-8.
Extension Cord Data
When calculating max. cord length, remember to include conductor length from
line disconnect device to input power receptacle.
NOTE
Input Voltage
Input Power
Phase
Hertz
Fuse Size Or
Circuit Breaker Rating
Conductor Size
Max. Cord Length
208 V
1
50/60
Time-Delay
2
40 A
Normal Operating
3
50 A
10 AWG
80 ft (24 m)
230 V
1
50/60
Time-Delay
2
35 A
Normal Operating
3
45 A
10 AWG
98 ft (30 m)
2 “Time-Delay” fuses are UL class “RK5” .
3 “Normal Operating” (general purpose – no intentional delay) fuses are UL class “K5” (up to and including 60 amp), and UL class “H” ( 65 amp and
above).