© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
Rev.1.1
2 / 2
Enclosure
Plastic, type PC (UL 94 V-0)
Net dimensions (d
x
w
x
h): 93x53x58 mm
Recommended space for installation (d
x
w
x
h): 100x60x70mm
Color: Light Grey. RAL 7035
Mounting
Wall.
DIN rail EN60715 TH35.
Terminal Wiring
(for power supply and
low-voltage signals)
Per terminal: solid wires or stranded wires (twisted or with
ferrule)
1 core: 0.5mm
2
… 2.5mm
2
2 cores: 0.5mm
2
… 1.5mm
2
3 cores: not permitted
Power
1 x Plug-in screw terminal block (3 poles)
Positive, Negative, Earth
9-24VDC +/-10% Max.: 205mA
Ethernet
1 x Ethernet 10/100 Mbps RJ45
2 x Ethernet LED: port link and activity
Port
1 x Serial EIA485 (Plug-in screw terminal block 3 poles)
A, B, SGND (Reference ground or shield)
1500VDC isolation from other ports
Operation
Temperature
0°C to +60°C
Operational
Humidity
5 to 95%, no condensation
Protection
IP20 (IEC60529)
CONNECTIONS
ELECTRICAL & MECHANICAL FEATURES
Power Supply
Must use NEC Class 2 or Limited Power Source (LPS) and SELV
rated power supply.
Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within
the range admitted (check table below). The power supply can be connected to earth
but only through the negative terminal, never through the positive terminal.
Ethernet
Connect the cable coming from the IP network to the connector ETH of the Intesis
gateway. Use an Ethernet CAT5 cable. If communicating through the LAN of the
building, contact the network administrator and make sure traffic on the port used is
allowed through all the LAN path (check the Intesis gateway user manual for more
information). With factory settings, after powering up the Intesis gateway, DHCP will
be enabled for 30 seconds. After that time, if no IP is provided by a DHCP server,
the default IP 192.168.100.246 will be set.
Port Modbus RTU
Connect the EIA485 bus to connectors A (B+), B (A-) and SG (SNGD) of Intesis
gateway’s Port. Respect the polarity.
Note for EIA485 port; Remember the characteristics of the standard EIA485 bus:
maximum distance of 1200 meters, maximum 32 devices connected to the bus, and
in each end of the bus it must be a termination resistor of 120 Ω.
Power
Supply
Modbus
RTU
Ethernet
Modbus TCP
70mm (h)
60 mm (w)
100 mm (d)
This marking on the product, accessories, packaging or literature (manual) indicates that the product contains electronic
parts and they must be properly disposed of by following the instructions at
https://intesis.com/weee-regulation
Port
A1A2A3
E
T
H
-
P
o
rt
A