Enclosure 

Plastic, type PC (UL 94 V-0) 
Net dimensions (d

x

w

x

h): 93x53x58 mm  

Recommended space for installation (d

x

w

x

h): 100x60x70mm 

Color: Light Grey. RAL 7035 

 

Mounting 

Wall. 
DIN rail EN60715 TH35. 

 

Terminal Wiring 

(for power supply and 
 low-voltage signals) 

Per terminal: solid wires or stranded wires (twisted or with 
ferrule) 

1 core: 0.5mm

2

… 2.5mm

2

 

2 cores: 0.5mm

2

… 1.5mm

2

 

3 cores: not permitted 

 

Power 

1 x Plug-in screw terminal block (3 poles) 

Positive, Negative, Earth 
9-24VDC +/-10% Max.: 205mA 

 

Ethernet 

1 x Ethernet 10/100 Mbps RJ45 
2 x Ethernet LED: port link and activity 

 

Port  

1 x Serial EIA485 (Plug-in screw terminal block 3 poles) 
         A, B, SGND (Reference ground or shield) 

1500VDC isolation from other ports 

 

Operation 
Temperature 

 0°C to +60°C 

 

Operational 
Humidity 

5 to 95%, no condensation 

 

 
Protection

 

IP20 (IEC60529)

  

 

CONNECTIONS 

ELECTRICAL & MECHANICAL FEATURES 

Power Supply 
Must use NEC Class 2 or Limited Power Source (LPS) and SELV

 

rated power supply. 

Respect polarity applied of terminals (+) and (-). Be sure the voltage applied is within 
the range admitted (check table below). The power supply can be connected to earth 
but only through the negative terminal, never through the positive terminal.  
 
Ethernet 
Connect the cable coming from the IP network to the connector ETH of the  Intesis 
gateway.  Use  an  Ethernet  CAT5  cable.  If  communicating  through  the  LAN  of  the 
building, contact the network administrator and make sure traffic on the port used is 
allowed through all the LAN path (check the Intesis gateway user manual for more 
information). With factory settings, after powering up the Intesis gateway, DHCP will 
be enabled for 30 seconds. After that time, if no IP is provided by a DHCP server, 
the default IP 192.168.100.246 will be set. 
 
Port Modbus RTU 
Connect  the  EIA485  bus  to  connectors  A  (B+),  B  (A-)  and  SG  (SNGD)  of  Intesis 
gateway’s Port. Respect the polarity. 
 
Note for EIA485 port; Remember the characteristics of the standard EIA485 bus: 
maximum distance of 1200 meters, maximum 32 devices connected to the bus, and 
in each end of the bus it must be a termination resistor of 120 Ω.  

Power 
Supply 

Modbus 

RTU 

Ethernet 
Modbus TCP 

 

70mm (h) 

60 mm (w) 

100 mm (d) 