3.
Quick Start Guide
1.
Disconnect the Hydro unit from the Mains Power.
2.
Attach the interface next to the Hydro unit (wall mounting) following the instructions of
the diagram above or install it inside the Hydro unit (respect the safety instructions
given by Panasonic).
3.
Connect the provided cable of the Panasonic interface between the Hydro unit and the
Intesis interface following the instructions of the diagram above.
4.
Connect the EIA-485 bus to the connector
EIA485
of the interface.
5.
Close the Hydro indoor unit.
6.
Check the DIP-Switch configuration of the Intesis interface and make sure it matches the
current installation’s parameters (see section
By default, the interface is set to:
▪
Modbus Slave Address
➔
1
▪
Modbus baud rate
➔
9600 bps
These parameters can be modified from SW4 and SW3 DIP-Switches.
All other switch positions are set at low level (Off position ) by default.
NOTE:
All changes on the DIP-Switch configuration require a system power cycle to be
applied.
7.
Connect the Hydro unit system to Mains Power.
IMPORTANT:
The Intesis interface requires to be connected to the Hydro unit
(powered) to start communicating.
ON
ON
SW3
SW4