INMBSMID---I000
User’s Manual r
1.3 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL https://www.intesis.com
10 / 24
Register Address
(protocol address)
Register Address
(PLC address)
R/W Description
7
8
R/W
INMBSMID001I000 Disablement
4
▪
0: INMBSMID001I000 enabled (Default)
▪
1: INMBSMID001I000 disabled
8
9
R/W
4,5
▪
0: Remote enabled (Default Value)
▪
1: Remote disabled
9
10
R/W
▪
0..65535 (hours). Counts the time the
AC unit is in “On” state.
10
11
R
AC unit Alarm Status
▪
0: No alarm condition
▪
1: Alarm condition
11
12
R
Error Code
6
▪
0: No error active
▪
65535 (-1 if it is read as signed value):
Error in the communication of
INMBSMID001I000 with the AC unit
▪
Any other error present, see the table at
the end of this document. (Section 7)
22
23
R/W
Indoor unit ambient temperature from
external sensor (at Modbus side)
▪
-32768: (Initialization value). No
temperature is being provided from an
external sensor.
▪
Any other: (ºC/x10ºC/ºF)
23
24
R
▪
-32678 (Initialization value)
▪
17..30 ºC (ºC/x10ºC)
▪
63..86 ºF
66
67
R
▪
-32768 (Initialization value)
▪
Ranges determined by the Manufacturer
of the AC indoor unit. (ºC/x10ºC/ºF)
97
98
R/W
4,8,9
▪
0: Non-blocked (Default value)
▪
1: Blocked
4
This value is stored in non-volatile memory
5
This register blocks the
Remote Controller’s
communication installed in the MD-RC bus (if this one has been installed).
6
See section 7 for possible error codes and their explanation
7
See section 4.4 for more information
8
If the register is configured as “0:
Non-
blocked”, all commands received from Modbus will be sent to the AC system. If “1:
Blocked”, commands from Modbus will only be sent to the AC system if they
differ from the previous value (values sent on change).
9
This register applies to firmware version 1.0 onwards