KNX
USER MANUAL
Issue date: 05/2018 r1.2 ENGLISH
Page 1: ...KNX USER MANUAL Issue date 05 2018 r1 2 ENGLISH...
Page 2: ...nd are only intended to help improve understanding of the functionality and handling of the product In view of the wide range of possible applications of the product and because of the many variables...
Page 3: ...URL https www intesis com 3 18 Gateway for the integration of KNX TP 1 EIB installations into Modbus RTU and or Modbus TCP enabled monitoring and control systems ORDER CODE LEGACY ORDER CODE INMBSKNX...
Page 4: ...s RTU 8 Modbus TCP 8 Address Map 8 Points definition 9 4 Connections 10 Powering the device 11 Connection to KNX 11 Connection to Modbus 11 4 3 1 Modbus TCP 11 4 3 2 Modbus RTU 11 Connection to the co...
Page 5: ...own KNX TP 1 EIB system and vice versa For this Intesis acts as a Modbus TCP server or Modbus RTU slave device in its Modbus interface allowing read write points from the Modbus client device s and o...
Page 6: ...X group address With this all the Modbus system is seen as one more KNX device from the KNX system point of view with the same configuration and operation characteristics When a change in any Modbus p...
Page 7: ...al point into Intesis is determined by the flags configured for the point See details in section 2 2 Points definition Every internal datapoint to define has the following KNX properties Property Desc...
Page 8: ...te Modbus registers Modbus functions 06 and 16 Single Multiple Holding Registers and Write Multiple Holding Registers can be used to write Modbus registers If poll records are used to read or write mo...
Page 9: ...ment C2 16 32 bits Float 16 bits Bitfields Error comm Function code One of the following Modbus function codes can be used 1 Read Coils 2 Read Discrete Inputs 3 Read Holding Registers 4 Read Input Reg...
Page 10: ...abled default IP is 192 168 100 246 PortA KNX Connect the KNX TP1 bus to connectors A3 and A4 of gateway s PortA Respect the polarity PortB Modbus RTU Connect the EIA485 bus to connectors B1 B B2 A an...
Page 11: ...1 network to the KNX port of Intesis The cable to be used shall be a straight Ethernet UTP FTP CAT5 cable 4 3 2 Modbus RTU Connect the communication cable coming from the Modbus network to the port m...
Page 12: ...tegration are Intesis gateway Link to download the configuration tool Product documentation Intesis MAPS Configuration monitoring tool for Intesis KNX series 5 2 1 Introduction Intesis MAPS is a Windo...
Page 13: ...ubsets of information are shown in this window General Gateway general parameters KNX KNX interface configuration and Modbus Client Modbus interface parameters Figure 5 2 Intesis MAPS configuration ta...
Page 14: ...mmunication Console window Intesis will reboot automatically once the new configuration is loaded Figure 5 4 Intesis MAPS Receive Send tab After any configuration change do not forget to send the conf...
Page 15: ...HMS Industrial Networks S L U All rights reserved This information is subject to change without notice URL https www intesis com 15 18 Figure 5 5 Diagnostic More information about the Diagnostic secti...
Page 16: ...ply voltage applied WARNING In order to avoid earth loops that can damage Intesis and or any other equipment connected to it we strongly recommend The use of DC power supplies floating or with the neg...
Page 17: ...24VDC Push Button Button A Check the user manual Button B Check the user manual Operation Temperature 0 C to 60 C Ethernet 1 x Ethernet 10 100 Mbps RJ45 2 x Ethernet LED port link and activity Operat...
Page 18: ...reserved This information is subject to change without notice URL https www intesis com 18 18 7 Dimensions Recommended available space for its installation into a cabinet wall or DIN rail mounting wit...