AB7609 Installation Guide
2
© 2005 HMS Industrial Networks.
Installation Items Checklist
• Anybus-X
ProfiBus
to DeviceNet Gateway (part number AB7609).
•
Anybus-X ProfiBus to DeviceNet Gateway User Manual
downloadable from
http://www.anybus.com and go to the support section
• Power cable for connection to supplied 2 position connector.
• DeviceNet cable for connection to supplied 5 position connector.
• PROFIBUS cable for connection to 9-pin D-Subminiature connector.
• DeviceNet configuration tool such as RSNetworx for DeviceNet or NetTool-
DN.
• PROFIBUS configuration tool.
• EDS file,
EDS_ABM_DEV_V_1_3.eds
, downloadable from:
http
://www.anybus.com and go to the support section
.
• GSD file, HMS_1013.gsd, downloadable from
http://www.anybus.com and go
to the support section
.
Installation and operating requirements
•
Power, input and output (I/O) wiring must be in
accordance with Class 1, Division 2 wiring methods
– article 501-4 (b) of the National Electric code,
NFPA 70 and in accordance with local codes.
•
Warning – Explosion Hazard
– Substitution of
components may impair suitability for class 1,
Division 2.
•
Warning – Explosion Hazard
– When in hazardous
locations turn off power before replacing or wiring
modules.
•
Warning – Explosion Hazard
– Do not disconnect
equipment unless power has been switched off or the
area is known to be nonhazardous.
•
Terminal tightening torque must be between 5 – 7
lbs-in (0,5-0,8 Nm).
•
For use in Class 2 circuits only.
•
Suitable for Surrounding temperature of 65 C max.
•
Use 60/75 C copper wire only.