3.3.3 Broadcast signals
Broadcast signals allow to control all ballasts in the same line from an individual signal.
Supported signals vary according to device type, configured through Intesis MAPS.
Following abbreviations are done in the table:
•
FL: Fluorescent light (device type 0)
•
EML: Emergency light (device type 1)
•
LED: LED module (device type 6)
TOPIC
Ballast /
Device Type
NAME
LEN
DATAPOINT TYPE
FLAGS
FUNCTION
FL
EM
L
L
E
D
DPT_NAME
DPT_ID
U
T
Ri
W
R
COMM
ERR
x
x
x
Arc Power Level
1 bit
DPT_Alarm
1.005
U
Ri
W
R
0 to 100 %
x
x
x Arc Power Off / On
1 bit
DPT_Switch
1.001
U
Ri
W
R
0-Off; 1-100 %
x
x
x Step Down / Up
1 bit
DPT_Step
1.007
U
Ri
W
R
0-Step Down
1-Step Up
x
x
x Recall Min Level
1 bit
DPT_Start
1.010
U
Ri
W
R
1-Recall Min Level
x
x
x Recall Max Level
1 bit
DPT_Start
1.010
U
Ri
W
R
1-Recall Max Level
x
x
x Go to Scene
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Store Current Level as Scene
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Clear/Remove Scene
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Set Fade Time
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Set Fade Rate
1 byte
Unsigned Value
5.x
U
Ri
W
R
1 to 15
FLAGS:
If marked with a
black
"
x
" will be enabled by default and couldn't be disabled.
If marked with
red
"
x
"
, column will be disabled by default but could be enabled by user.
If marked with
blue
"
x
"
, column will be enabled by default but could be disabled by user.