Intesis
TM
KNX
– DALI
User Manual r1.0 EN
© HMS Industrial Networks S.L.U - All rights reserved
This information is subject to change without notice
URL
http
s
://www.intesis.com
11 / 41
x
x
x Store Current Level as Scene
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Clear/Remove Scene
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Add to DALI Group
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 15
x
x
x Remove from DALI Group
1 byte
Unsigned Value
5.x
U
Ri
W
R
1 to 15
x
x
x Set Fade Time
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 100 %
x
x
x Set Fade Rate
1 byte
Unsigned Value
5.x
U
Ri
W
R
0 to 100 %
x
x
x Set Min Level
1 byte
DPT_Scaling
5.001
U
Ri
W
R
0 to 100 %
x
x
x Set Max Level
1 byte
DPT_Scaling
5.001
U
Ri
W
R
0 to 100 %
Set Power-on Level
1 byte
DPT_Scaling
5.001
U
Ri
W
R
0 to 100 %
x
Set System-failure Level
1 byte
DPT_Scaling
5.001
U
Ri
W
R
0 to 100 %
x
Failure Status
1 byte
Unsigned Value
5.x
T
R
b7-FunctFail
b6-DurFail
b5-DurTestDelay
b4-FunctTestDelay
b3-EmLampFail
b2-BattFail
b1-BattDurFail
b0-CircFail