A2 VFD
(0.75-30kW)
12
Chapter 7 Description of Configure Parameters
Pn 01
Default display content
:
1
——
30000
RUN
:
1 means it will display runtime frequency
Otherwise, it displays motor’s synchronization speed. 2
——
30000 is motor synchronization speed
STOP
:
it will display frequency given by external signal.
Pn 02
Initial startup frequency by panel or other method Range
:
000.01Hz
-
400.00Hz
,
the initial panel data and
external signal frequency during startup
.
Pn 03
Source of runtime frequency with range
:
1—7
1 Potentiometer
2 Panel button
3 External 0-5V signal
4 External 0-10V signal
5 External 0-20mA signal
6 External digital signal
7 Multi-segment signal
Pn 04
Source of runtime command with range
:
1—2
1 Panel button control
2 External signal control
Pn 05
clockwise / anticlockwise disable with range
:
1—3
1 clockwise enable only
2 anticlockwise enable only
3 clockwise / anticlockwise enable
Pn 06
Method to stop VFD with range
:
1—2
1 stop by itself
2 stop by deceleration
Pn 07
Start again by external signal with range
:
1—2
1 disable
2 enable
Description: when the power on the external operation of
the signal is allowed to start effectively.
Pn 08
Acceleration time with range
:
000.01S
-
650.00S
Accelerate time (from 0Hz to Pn10).
Summary of Contents for VFD Drive A2 Series
Page 1: ...A2 VFD 0 75 30kW HKS VFD Drive A2 Series User Manual ...
Page 28: ...A2 VFD 0 75 30kW 25 第 2 步 Step 2 手指缺口处用力拉起 Pull up the finger gap ...
Page 29: ...A2 VFD 0 75 30kW 26 第 3 步 Step 3 ...
Page 34: ...A2 VFD 0 75 30kW 第 2 步 Step 2 31 手指缺口处用力拉起 Pull up the finger gap ...
Page 35: ...A2 VFD 0 75 30kW 32 第 3 步 Step 3 ...
Page 37: ...A2 VFD 0 75 30kW 第 2 步 Step 2 34 轻轻按入 Press in gently ...
Page 38: ...A2 VFD 0 75 30kW 35 第 3 步 Step 3 ...
Page 39: ...A2 VFD 0 75 30kW 36 ...
Page 40: ...A2 VFD 0 75 30kW 37 ...
Page 41: ...A2 VFD 0 75 30kW 38 ...
Page 42: ...A2 VFD 0 75 30kW 39 ...
Page 43: ...A2 VFD 0 75 30kW 40 ...
Page 44: ...A2 VFD 0 75 30kW 41 ...